Final | 1/8/2015 | 1/9/2015 | 1/9/2015 | A | FAIL |
Rock A. Hudson
|
|
|
The code for door is AHC for lock box on back door. Home is vacant Phone #: ###-#### Inspection requested via web by Randy Fletcher 240.24(D)- Overcurrent devices shall not be located in the vicinity of easily ignitible material, such as clothes closets. 240.4- Max overcurrent for protection of conductors- 14 ga 15 amp max, 10 ga 30 amp max. 210.4(D)- Check multi-wire branch circuits for proper phasing to ensure grounded conductor does not carry current from both legs. *New wire dated 2013 in panel for furnace and master bath not on permit. 210.52- Receptacle outlet spacing in master bed and kitchen counter top areas does not comply with 210.52. *Record of 2 notices given to pull permits for remodel work, MIS14-00273, MIS14-00314.
|