Final | 5/23/2014 | 5/27/2014 | 5/27/2014 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Louis Keller ok final
|
Electrical Rough-In | 4/14/2014 | 4/15/2014 | 4/15/2014 | A | PASS |
Bob Reichert
|
|
|
Underground Phone #: ###-#### >> Inspection requested via web by Louis Keller corrections made, u/g and potting only ok
|
Final | 4/6/2014 | 4/7/2014 | 4/7/2014 | A | FAIL |
Bob Reichert
|
|
|
Potting and underground Phone #: ###-#### >> Inspection requested via web by Louis Keller called, left message, left correction notice, NEC 680.10 u/g raceways shall be minimum 18" deep, 310.15(B)2(b) shall maintain conduit spacing, 350.26 there shall not be more than 360 degree total bends
|
Electrical Rough-In | 3/24/2014 | 3/25/2014 | 3/25/2014 | A | PASS |
Bob Reichert
|
|
|
Bonding inspection Phone #: ###-#### >> Inspection requested via web by Louis Keller pool bonding only ok
|