Final | 5/21/2014 | 5/22/2014 | 5/22/2014 | A | PASS |
Bob Reichert
|
|
|
ELE-INSPECTOR ok final
|
Rough-In Permanent Service | 4/17/2014 | 4/17/2014 | 4/17/2014 | P | PASS |
Bob Reichert
|
|
|
corrections made, ri ok p/s u/g n ok
|
Final | 4/17/2014 | 4/17/2014 | 4/17/2014 | P | CANC |
Bob Reichert
|
|
|
re inspect Phone #: ###-#### >> Inspection requested via web by Greg Traudt corrections made, ri ok, p/s u/g n ok see rip
|
Rough-In Permanent Service | 4/15/2014 | 4/17/2014 | 4/17/2014 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Greg Traudt called, left correction notice, NEC 250.68 shall provide access to grounding electrode, 334.23 shall protect nm cable within 6' of attic access, 250.86 shall ground metal boxes
|