Final | 8/6/2014 | 8/6/2014 | 8/6/2014 | P | PASS |
Rex Boyles
|
|
|
Victoria Phone #: ###-#### or ###-#### corrections made
|
Final | 8/1/2014 | 8/1/2014 | 8/1/2014 | P | FAIL |
Rex Boyles
|
|
|
Victoria Phone #: ###-#### all outside conv. outlets need GFCI protection
|
Final | 7/30/2014 | 7/31/2014 | 7/31/2014 | A | FAIL |
Rex Boyles
|
|
|
First thing in AM if possible please // Vicki Phone #: ###-#### exterior convenience outlets shall be GFCI protected 210.8(A)(3)
|
Electrical Rough-In | 6/5/2014 | 6/6/2014 | 6/6/2014 | A | PASS |
Rex Boyles
|
|
|
Request before 10 -Vicki Phone #: ###-#### rough in ok
|
Final | 5/27/2014 | 5/28/2014 | 5/28/2014 | A | CANC |
Rex Boyles
|
|
|
Early before 9 please - Victoria Phone #: ###-#### or ###-#### needed rough in inspection
|
Electrical Rough-In | 5/28/2014 | 5/28/2014 | 5/28/2014 | P | FAIL |
Rex Boyles
|
|
|
Early before 9 please - Victoria Phone #: ###-#### or ###-#### bring junction boxes down to ceiling and install plastic mud rings to make accessable in future, staple romex nm cable within 12" of box, install ground screws in metal boxes, install nailplates to protect nm cable, remove all devices for drywall installation.
|
Conference | 4/24/2014 | 5/2/2014 | 5/2/2014 | A | DONE |
Rex Boyles
|
|
|
early as poss// Vicki ###-#### or ###-#### discuss room addition
|