Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE14-00993
StatusFinaled
Name LARRYS ELECTRIC
Site Address 3300 W KOOTENAI ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Addition: Move and add outlets in kitchen
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In9/10/20149/10/20149/10/2014PCANC
DetailsRock A. Hudson
Phone #: ###-#### Needed final
Final9/10/20149/10/20149/10/2014PPASS
DetailsRock A. Hudson
Phone #: ###-#### Final ok
Final9/9/20149/9/20149/9/2014PFAIL
DetailsRock A. Hudson
Larry Phone #: ###-#### 210.8 Ground-Fault Circuit-Interrupter Protection for
Personnel. Ground-fault circuit-interrupter protection for
personnel shall be provided as required in 210.8(A) through
(D). The ground-fault circuit-interrupter shall be installed in
a readily accessible location.
Informational Note: See 215.9 for ground-fault circuitinterrupter
protection for personnel on feeders.
(A) Dwelling Units. All 125-volt, single-phase, 15- and
20-ampere receptacles installed in the locations specified in
210.8(A)(1) through (10) shall have ground-fault circuit interrupter protection for personnel.
(6) Kitchens — where the receptacles are installed to
serve the countertop surfaces
Electrical Rough-In4/24/20144/25/20144/25/2014APASS
DetailsRock A. Hudson
This is a re-inspect Phone #: ###-#### >> Inspection requested via web by Larry Richardson Kitchen remodel rough in ok cover
Rough-In Permanent Service4/23/20144/24/20144/24/2014AFAIL
DetailsRock A. Hudson
If no one in home check room above garage for owners Phone #: ###-#### >> Inspection requested via web by Larry 300.4(A)(2)- NM cable shall be ran in a notch or hole bored through stud not on surface with nail plate tacked over top.
300.4- NM cable ran through holes bored holes that are less than 1 1/4" from framing surface shall be protected from physical damage.
210.52(B)(2)- The two or mor small appliance branch circuits specified in 210.52 (B)(1) shall have no other outlets.
406.3(D)- grounding tye receptical outlets installed on non grounded circuits shall have GFCI protection