Permit Information
Permit NumberELE14-01029
StatusFinaled
Name JAY VANSCHOIACK
Site Address 970 E BRAEMERE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: New single family dwelling 200 amp service w/100 amp sub panel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/28/20148/28/20148/28/2014PPASS
DetailsRex Boyles
Jay Phone #: ###-#### final ok
Final8/27/20148/27/20148/27/2014PFAIL
DetailsRex Boyles
Jay Phone #: ###-#### 210.8-GFCI protection required for garage door openers receptacles
Final7/8/20147/9/20147/9/2014ACANC
DetailsRex Boyles
Re-inspect floor tile heat in 2 bathrooms. Upper was approved for cover 7/8/14. Bottom bathroom corrections have been made. Call Jay(###-####) if any ? Phone #: ###-#### >> Inspection requested via web by Jay VanSchoiack needed r/i
Electrical Rough-In7/9/20147/9/20147/9/2014PPASS
DetailsRex Boyles
Re-inspect floor tile heat in 2 bathrooms. Upper was approved for cover 7/8/14. Bottom bathroom corrections have been made. Call Jay(###-####) if any ? Phone #: ###-#### >> Inspection requested via web by Jay VanSchoiack correction made r/i ok dnst. floor heat
Electrical Rough-In7/8/20147/8/20147/8/2014PPART
DetailsBob Reichert
floor heat // Jay Phone #: ###-#### met contractor, called office to ad 2 floor heat to permit, ok cover upper floor heat, failed lower floor heat, correction notice posted
Electrical Rough-In7/7/20147/8/20147/8/2014AFAIL
DetailsRock A. Hudson
floor heat // Jay Phone #: ###-#### 110.3 Floor heat system shall be installed to manufacturers instructions. Cold lead splice, end termination, and sensor tip shall be recessed in floor to avoid damage.
Electrical Rough-In4/28/20144/29/20144/29/2014ACANC
DetailsRex Boyles
Jay Phone #: ###-#### needed perm. serv.
Rough-In Permanent Service4/29/20144/29/20144/29/2014PPASS
DetailsRex Boyles
Jay Phone #: ###-#### rough in ok to cover p/s u/g n ok
Electrical Rough-In4/25/20144/28/20144/28/2014AFAIL
DetailsRex Boyles
Phone #: ###-#### >> Inspection requested via web by Jay VanSchoiack finish rough in for deck conv. outlets and exterior lights. Add conv. oulets in dining room. Get clearance on recessed cans in basement mech. room. Loose wiring at central vac. outlet. 1/14 clearance at back door. fireplace rough in