Final | 9/9/2014 | 9/10/2014 | 9/10/2014 | A | PASS |
Daryl DeGrange
|
|
|
please call ahead for access, home is not occupied Phone #: ###-#### Inspection requested via web by David Nelson final ok
|
Electrical Rough-In | 6/23/2014 | 6/24/2014 | 6/24/2014 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson corrections made, ri ok
|
Electrical Rough-In | 6/20/2014 | 6/23/2014 | 6/23/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson NEC 300.4 Nail plates required where NM cable are less than 1 1/4 from edge of framing member( either side) NEC 334.30 Shall secure cable within 12 in. of entering service panel NEC 334.80 Shall not staple more than 3 NM cables together(stackets)
|
Final | 6/20/2014 | 6/23/2014 | 6/20/2014 | A | CANC |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Rough-In Permanent Service | 5/8/2014 | 5/8/2014 | 5/8/2014 | P | NR |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson Not ready for any cover
|
Permanent Service | 5/8/2014 | 5/8/2014 | 5/8/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson p/s o/h rec ok
|