Final | 7/17/2014 | 7/17/2014 | 7/17/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White Final ok
|
Final | 7/7/2014 | 7/7/2014 | 7/7/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Lock Box-12345 Phone #: ###-#### >> Inspection requested via web by Matthew White 210.52(C)- KItchen counter top spaces 12" or wider shall have receptical outlet installed. 406.12(A)- In dwelling units all areas specified in 210.52 120 volt 15 or 20 amp receptical outlets shall be tamper resistant type. Down bath GFI and back outlet under service. 410.16(A)(1)- Luminaires located in storage space shall have totally enclosed light sources. 314.25- Each box shall have covers
|
Electrical Rough-In | 5/23/2014 | 5/23/2014 | 5/23/2014 | P | PASS |
Rock A. Hudson
|
|
|
Kelly Phone #: ###-#### Basement and kitchen rewired main level existing. Rough in ok cover
|
Electrical Rough-In | 5/20/2014 | 5/20/2014 | 5/20/2014 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White met contractor, NEC 21.52 shall meet outlet spacing, shall provide 3-way switching and light for stairs to lower level, shall complete make-up, shall provide lighting outlet in storage spce as required
|
Permanent Service | 5/12/2014 | 5/12/2014 | 5/12/2014 | P | PASS |
Rock A. Hudson
|
|
|
Arron Phone #: ###-#### p/s o/h rec ok
|