Final | 5/23/2014 | 5/23/2014 | 5/23/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Final ok
|
Permanent Service | 5/13/2014 | 5/13/2014 | 5/13/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack p/s o/h n ok
|
Electrical Rough-In | 5/13/2014 | 5/13/2014 | 5/13/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack 400.5(A)- #8 SEOOW 3 current carrying conductor cord max ampacity 35 amps, 50 amp over current installed
|
Electrical Rough-In | 5/13/2014 | 5/13/2014 | 5/13/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack 400.5(A)- # 8 SEOOW 3 current carrying conductor cord max ampacity 35 amps, 50 amp over current installed.
|