Final | 6/30/2014 | 6/30/2014 | 6/30/2014 | P | PASS |
Rock A. Hudson
|
|
|
Jeff-call prior for access Phone #: ###-#### Final ok
|
Electrical Rough-In | 5/15/2014 | 5/15/2014 | 5/15/2014 | A | PASS |
Rock A. Hudson
|
|
|
thanks, Jeff ###-#### Phone #: ###-#### >> Inspection requested via web by Andrea Creek Rough in ok cover
|
Electrical Rough-In | 5/13/2014 | 5/14/2014 | 5/14/2014 | P | FAIL |
Bob Reichert
|
|
|
Please call Jeff at ###-#### when on way. Thanks, Andrea. Phone #: ###-#### >> Inspection requested via web by Andrea Creek called, shall install receptacles per NEC 210.52, 2' wall shall have outlet, outlets shall not be over 6' from doorway, shall provide access to inspect wall- no sheetrock in storage, old metal boxes not enough cubic inch, wires cut short, insulation shall be removed for inspection, BCC no violations shall be retained
|