Final | 10/9/2014 | 10/9/2014 | 10/9/2014 | P | PASS |
Bob Reichert
|
|
|
Call for access Phone #: 6299948 >> Inspection requested via mobile web by David McClellan ok final
|
Electrical Rough-In | 6/23/2014 | 6/24/2014 | 6/24/2014 | A | PASS |
Rock A. Hudson
|
|
|
Call for access Phone #: 6299948 >> Inspection requested via mobile web by David McClellan Rough in ok cover
|
Permanent Service | 6/24/2014 | 6/24/2014 | 6/24/2014 | P | PASS |
Rock A. Hudson
|
|
|
Call for access Phone #: 6299948 >> Inspection requested via mobile web by David McClellan p/s u/g rec ok
|
Electrical Rough-In | 6/18/2014 | 6/19/2014 | 6/19/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Call for access Phone #: 6299948 >> Inspection requested via mobile web by David McClellan 210.52(A)(1)- Recepticals in basement shall be installed so no point measured along floor line is more than 6" from receptidal outlet. 210.52(A)(2)- In bedroom wall 24" and wider shall have receptical outlets installed. 314.16- Basement receptical outlet boxes shall have adequate room for box fill. 10 cubic in. min.
|