Final | 9/8/2014 | 9/8/2014 | 9/8/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lars Johnson Final ok
|
Final | 9/4/2014 | 9/5/2014 | 9/5/2014 | A | FAIL |
Rex Boyles
|
|
|
Call if no access. Phone #: ###-#### Inspection requested via web by Lars Johnson210.8(B)(2)-- all 120volt receptacles in kitchen area shall be GFCI protected.
|
Electrical Rough-In | 8/1/2014 | 8/1/2014 | 8/1/2014 | P | FAIL |
Rex Boyles
|
|
|
ceiling grid for access call 86992600 Phone #: ###-#### Inspection requested via web by Lars Johnson 330.30(B)-secure MC cable within 6" of box, recessed can lights need seismic wire with identification, close up junction boxes
|
Electrical Rough-In | 6/17/2014 | 6/18/2014 | 6/18/2014 | A | PASS |
Rex Boyles
|
|
|
Rough-in of electrical in island bar. Framing/cabinetry to protect conduits coming out of floor. Phone #: ###-#### >> Inspection requested via web by Lars Johnson rough in ok to cover
|
Electrical Rough-In | 6/2/2014 | 6/3/2014 | 6/3/2014 | A | PASS |
Rock A. Hudson
|
|
|
(2) underground 3/4" conduits for island counter Phone #: ###-#### >> Inspection requested via web by Lars Johnson Rough in ok cover
|