Permit Information
Permit NumberELE14-01452
StatusFinaled
Name CORNERSTONE ELECTRIC
Site Address 20 S PEASLEY ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: remodle
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/19/20149/19/20149/19/2014PPASS
DetailsRock A. Hudson
code 1998 Phone #: ###-#### Inspection requested via web by cal crosby Final ok
Final9/18/20149/18/20149/18/2014PFAIL
DetailsRock A. Hudson
code 1998, if needed box is on side door Phone #: ###-#### Inspection requested via web by cal crosby 356.30 Securing and Supporting. Type LFNC-B shall be
securely fastened and supported in accordance with one of
the following:
(1) Where installed in lengths exceeding 1.8 m (6 ft), the
conduit shall be securely fastened at intervals not exceeding
900 mm (3 ft) and within 300 mm (12 in.) on each
side of every outlet box, junction box, cabinet, or fitting. AC whip.
200.7(C) Circuits of 50 Volts or More. The use of insulation
that is white or gray or that has three continuous white or
gray stripes for other than a grounded conductor for circuits
of 50 volts or more shall be permitted only as in (1) and (2).
(1) If part of a cable assembly that has the insulation permanently
reidentified to indicate its use as an ungrounded
conductor by marking tape, painting, or other
effective means at its termination and at each location
where the conductor is visible and accessible.
440.4 Marking on Hermetic Refrigerant Motor-
Compressors and Equipment. (C) Branch-Circuit Selection Current. A hermetic refrigerant
motor-compressor, or equipment containing such a
compressor, having a protection system that is approved for
use with the motor-compressor that it protects and that permits
continuous current in excess of the specified percentage
of nameplate rated-load current given in 440.52(B)(2)
or (B)(4) shall also be marked with a branch-circuit selection
current that complies with 440.52(B)(2) or (B)(4). This
marking shall be provided by the equipment manufacturer
and shall be on the nameplate(s) where the rated-load current(
s) appears.
110.12 Mechanical Execution of Work. Electrical equipment
shall be installed in a neat and workmanlike manner.
Informational Note: Accepted industry practices are described
in ANSI/NECA 1-2010, Standard Practice of Good
Workmanship in Electrical Construction, and other ANSIapproved
installation standards.
(A) Unused Openings. Unused openings, other than those
intended for the operation of equipment, those intended for
mounting purposes, or those permitted as part of the design
for listed equipment, shall be closed.
Electrical Rough-In6/5/20146/5/20146/5/2014APASS
DetailsRock A. Hudson
Code in lock box on front door # 3536 Phone #: ###-#### >> Inspection requested via web by cal crosby Rough in ok cover