Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberELE14-01539
StatusFinaled
Name STEPHANIE SAYEGH
Site Address 116 S RANDALL ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/16/201611/16/201611/16/2016PPASS
DetailsEric Story
jalal - call 15 mins prior Phone #: ###-####
corrections fixed final ok
Final11/7/201611/7/201611/7/2016PFAIL
DetailsEric Story
Jalal Phone #: ###-####-pleae call 15 minutes prior
406.4 Tamper resistant receptales required(throu out)and weather resistant for all exterior receptacles
410.16 Luminaires in closets shall be totally enclosed and shall maintain 12" from shelfs in closets
210.(5) Seperate counter spaces shall receptacles located with 6" of edge@12" from top of counter
210.12 AFCI protection required for all bedrooms
250.94 Intersystem bond required for other systems
Electrical Rough-In10/2/201410/2/201410/2/2014PPASS
DetailsRock A. Hudson
Jalal Phone #: ###-#### Complete house wiring Rough in ok cover
Electrical Rough-In9/30/20149/30/20149/30/2014PFAIL
DetailsRock A. Hudson
Jalal// please call before Phone #: ###-#### 250.96 Bonding Other Enclosures.
(A) General. Metal raceways, cable trays, cable armor,
cable sheath, enclosures, frames, fittings, and other metal
non–current-carrying parts that are to serve as equipment
grounding conductors, with or without the use of supplementary
equipment grounding conductors, shall be bonded
where necessary to ensure electrical continuity and the capacity
to conduct safely any fault current likely to be imposed on them.
210.11(C)(3) Bathroom Branch Circuits. In addition to the number
of branch circuits required by other parts of this section, at
least one 120-volt, 20-ampere branch circuit shall be provided
to supply a bathroom receptacle outlet(s). Such circuits
shall have no other outlets.
210.52(A)(2) Wall Space. As used in this section, a wall space shall
include the following:
(1) Any space 600 mm (2 ft) or more in width (including
space measured around corners) and unbroken along
the floor line by doorways and similar openings, fireplaces,
and fixed cabinets.
300.4 Protection Against Physical Damage. Where subject
to physical damage, conductors, raceways, and cables
shall be protected.
334.30-Flat cables shall not be
stapled on edge.
110.3- Smoke detector wiring shall be complete.
Permanent Service9/30/20149/30/20149/30/2014PPASS
DetailsRock A. Hudson
Jalal// please call before Phone #: ###-#### p/s o/h n ok