Final | 11/16/2016 | 11/16/2016 | 11/16/2016 | P | PASS |
Eric Story
|
|
|
jalal - call 15 mins prior Phone #: ###-#### corrections fixed final ok
|
Final | 11/7/2016 | 11/7/2016 | 11/7/2016 | P | FAIL |
Eric Story
|
|
|
Jalal Phone #: ###-####-pleae call 15 minutes prior 406.4 Tamper resistant receptales required(throu out)and weather resistant for all exterior receptacles 410.16 Luminaires in closets shall be totally enclosed and shall maintain 12" from shelfs in closets 210.(5) Seperate counter spaces shall receptacles located with 6" of edge@12" from top of counter 210.12 AFCI protection required for all bedrooms 250.94 Intersystem bond required for other systems
|
Electrical Rough-In | 10/2/2014 | 10/2/2014 | 10/2/2014 | P | PASS |
Rock A. Hudson
|
|
|
Jalal Phone #: ###-#### Complete house wiring Rough in ok cover
|
Electrical Rough-In | 9/30/2014 | 9/30/2014 | 9/30/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Jalal// please call before Phone #: ###-#### 250.96 Bonding Other Enclosures. (A) General. Metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings, and other metal non–current-carrying parts that are to serve as equipment grounding conductors, with or without the use of supplementary equipment grounding conductors, shall be bonded where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed on them. 210.11(C)(3) Bathroom Branch Circuits. In addition to the number of branch circuits required by other parts of this section, at least one 120-volt, 20-ampere branch circuit shall be provided to supply a bathroom receptacle outlet(s). Such circuits shall have no other outlets. 210.52(A)(2) Wall Space. As used in this section, a wall space shall include the following: (1) Any space 600 mm (2 ft) or more in width (including space measured around corners) and unbroken along the floor line by doorways and similar openings, fireplaces, and fixed cabinets. 300.4 Protection Against Physical Damage. Where subject to physical damage, conductors, raceways, and cables shall be protected. 334.30-Flat cables shall not be stapled on edge. 110.3- Smoke detector wiring shall be complete.
|
Permanent Service | 9/30/2014 | 9/30/2014 | 9/30/2014 | P | PASS |
Rock A. Hudson
|
|
|
Jalal// please call before Phone #: ###-#### p/s o/h n ok
|