Final | 6/27/2014 | 6/27/2014 | 6/27/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack correction done, final ok
|
Permanent Service | 6/19/2014 | 6/19/2014 | 6/19/2014 | A | PASS |
Daryl DeGrange
|
|
|
SE corner of Fairview & Fivemile, call Norm with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack p/s o/h n ok
|
Electrical Rough-In | 6/19/2014 | 6/19/2014 | 6/19/2014 | P | FAIL |
Daryl DeGrange
|
|
|
SE corner of Fairview & Fivemile, call Norm with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Required dead front missing front service panel in vending trailer, NEC 400.5 Table Columm A 8 AWG ampacity 35 ampere for flexible cord. All 120 volt 15 and 20 ampere receptacles require GFCI protection
|