Final | 7/29/2014 | 7/29/2014 | 7/29/2014 | P | PASS |
Rock A. Hudson
|
|
|
please contact Jason tomlinson for access ###-#### Phone #: ###-#### >> Inspection requested via web by michael hunt Final ok
|
Final | 7/22/2014 | 7/23/2014 | 7/23/2014 | P | FAIL |
Rex Boyles
|
|
|
please contact jason tomlinson after checking in at front desk ###-####, thank you mike rse ###-#### Phone #: ###-#### Inspection requested via web by michael hunt 605.7 multiwire branch circuits supplying power to permanently connected freestanding partitions shall be provided with a means to disconnect simultaneously all ungrounded conductors at the panel. Identify circuits in panel and somewhere on partitions.
|
Final | 7/22/2014 | 7/23/2014 | 7/22/2014 | A | CANC |
Rex Boyles
|
|
|
Mike Phone #: ###-#### Inspection cancelled from web by: michael hunt
|
Final | 7/2/2014 | 7/2/2014 | 7/2/2014 | P | PART |
Rex Boyles
|
|
|
ID Power building access call Jason Tomlinson ###-#### thank you, mike Phone #: ###-#### >> Inspection requested via web by michael hunt ceilings ok to cover only. please call for final after furniture installed
|
Electrical Rough-In | 6/19/2014 | 6/20/2014 | 6/20/2014 | P | PASS |
Rex Boyles
|
|
|
6th floor, new office walls ok to cover. contact # is ###-#### Jason Tomlinson ID. Power employee Phone #: ###-#### >> Inspection requested via web by michael hunt rough in walls ok
|