Final | 6/25/2014 | 6/25/2014 | 6/25/2014 | P | PASS |
Daryl DeGrange
|
|
|
Please call 1/2 hour before heading to job so that I can meet you to go over the listing on the materials used in the lighting retrofit. Thanks and have a great day Phone #: ###-#### >> Inspection requested via web by jason shifflett correction done, final ok
|
Final | 6/21/2014 | 6/23/2014 | 6/23/2014 | A | FAIL |
Daryl DeGrange
|
|
|
This Is A Idaho Power Lighting Upgrade And We Changed All Outlets To Tamperproof As Well As New Led E-Lights And Exit Signs On Existing Openings. Please Call Joe At ###-####. Thanks And Have A Great Day! Phone #: ###-#### >> Inspection requested via web by jason shifflett Lighting retros require rough-in inspections to check listed material. Bathroom GFCI has reverse polarity NEC 422.52 Drinking fountains require GFCI protection. End cap in florscent fixture requires KO seal
|