Final | 12/12/2014 | 12/12/2014 | 12/12/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson correction done, final ok
|
Final | 12/5/2014 | 12/5/2014 | 12/5/2014 | P | FAIL |
Cevyn Recla
|
|
|
Door has lock box code is 3412 the garage is detached code is the same as lock box 3412 Phone #: ###-#### Inspection requested via web by Zane Robertson Left message for contractor 210.8 GFI protection required - unfinished basement 210.8 GFI Protection required , counters in kitchens BCC- all items ready for inspection, kitchen not finished 225.32 disconnecting means shall be readily accessible and located at nearest point of entrance 110.22 Each disconnecting means shall be legigly marked to identify its purpose.
|
Rough-In Permanent Service | 7/2/2014 | 7/3/2014 | 7/3/2014 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson. P/S Connect ok. Ok to cover
|