Final | 9/19/2014 | 9/19/2014 | 9/19/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer final ok
|
Final | 9/18/2014 | 9/18/2014 | 9/18/2014 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer bathroom receptacles and GFCI not functioning, 210.8 (A) (2)- all receptacles in garages shall be GFCI protected, laundry room switch/plug combo not working, label shop panel, lockoff for dishwasher missing mechanism.
|
Electrical Rough-In | 7/11/2014 | 7/11/2014 | 7/11/2014 | A | PASS |
Rex Boyles
|
|
|
this inspection is for the detached garage---for cover only Phone #: ###-#### >> Inspection requested via web by ron spen cer r/i shop ok
|
Rough-In Permanent Service | 7/3/2014 | 7/7/2014 | 7/7/2014 | P | PASS |
Rex Boyles
|
|
|
roughin for house only at this time Phone #: ###-#### >> Inspection requested via web by ron spen cer r/i and u.g. to shop ok to cover. p/s u/g n ok
|