Final | 10/8/2015 | 10/8/2015 | 10/8/2015 | P | PASS |
Daryl DeGrange
|
|
|
Final Area E 1st-3rd Floor Common Areas, Hallway and Electrical Rooms to close out Permit. Contact Craig Timmons @ ###-#### or Bob Mott @ ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek final ok
|
Final | 9/22/2015 | 9/23/2015 | 9/23/2015 | A | PART |
Bob Reichert
|
|
|
Final for PD1, PD5, PD6, Stairwell E and PE2, PE3 and PE4. Contact Bob Mott at ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek rooms as requested ok for final
|
Final | 9/18/2015 | 9/21/2015 | 9/21/2015 | P | PART |
Bob Reichert
|
|
|
E1 Final Contact Craig Timmons Phone #: ###-#### Inspection requested via web by Cathy Duchek need to inspect balconies
|
Final | 8/27/2015 | 8/28/2015 | 8/28/2015 | P | PART |
Bob Reichert
|
|
|
Main Building Area E (Rooms E301-E310; 3rd floor hallway E; 2nd floor hallway; E201-E210) Contact Bob Mott Phone #: ###-#### Inspection requested via web by Cathy Duchek ok final as requested except for patios
|
Electrical Rough-In | 8/27/2015 | 8/28/2015 | 8/28/2015 | P | PASS |
Bob Reichert
|
|
|
Main Building Area E, 1st Floor E Hallway Ceiling Inspection. Contact Bob Mott Phone #: ###-#### Inspection requested via web by Cathy Duchek ok cover as requested
|
Final | 8/12/2015 | 8/13/2015 | 8/13/2015 | P | PART |
Bob Reichert
|
|
|
Final for D 2nd floor units rough in elevator lobby PE2 Phone #: ###-#### Inspection requested via web by Fabian Luna ok partial, 6 rooms, ok as requested to cover
|
Electrical Rough-In | 8/10/2015 | 8/11/2015 | 8/11/2015 | P | PASS |
Bob Reichert
|
|
|
CEILING COVER FOR GRID CEILING E SECOND FLOOR CORRIDOR Phone #: ###-#### Inspection requested via web by Fabian Luna ok cover as requested
|
Electrical Rough-In | 8/6/2015 | 8/6/2015 | 8/6/2015 | P | PASS |
Bob Reichert
|
|
|
CEILING COVER FOR CORRIDOR E351 Phone #: ###-#### Inspection requested via web by Fabian Luna ok cover as requested
|
Final | 6/12/2015 | 6/12/2015 | 6/12/2015 | A | PART |
Bob Reichert
|
|
|
Final inspection for IL area C all rooms on all floors as balcony railings are finished and exterior lights and GFCI receptacles can be tested. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum c ok, signed t/o card
|
Final | 6/10/2015 | 6/10/2015 | 6/10/2015 | P | PART |
Bob Reichert
|
|
|
Final inspection IL area D garage rooms PD1-PD6. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok final as requested
|
Final | 6/8/2015 | 6/8/2015 | 6/8/2015 | P | PART |
Bob Reichert
|
|
|
Final inspection IL stairwells C1, C2. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum part final as requested
|
Final | 6/4/2015 | 6/5/2015 | 6/5/2015 | P | PART |
Daryl DeGrange
|
|
|
Final inspection corridors and misc support rooms IL area C 1st, 2nd, and 3rd floor rooms. D Commons 1st floor all rooms. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Partial finalok
|
Electrical Rough-In | 5/22/2015 | 5/26/2015 | 5/26/2015 | A | PASS |
Bob Reichert
|
|
|
Wall rough in IL 1st floor area E rooms E153 ; E154. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 5/21/2015 | 5/21/2015 | 5/21/2015 | P | PASS |
Bob Reichert
|
|
|
T-grid ceiling inspection IL area D 2nd floor Corridors D251 ; D252. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum left correction notice, NEC 110.26(A)(1) depth of working space shall be minimum 42" in basement electrical room, west side, ok cover as requested
|
Final | 5/19/2015 | 5/19/2015 | 5/19/2015 | P | PART |
Bob Reichert
|
|
|
Final inspection IL area C 1st floor room C101. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok except outdoor receptacle
|
Final | 5/15/2015 | 5/15/2015 | 5/15/2015 | A | PART |
Bob Reichert
|
|
|
Final inspection IL 2nd floor area B rooms C201-C210. Building permit BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok except balconies
|
Final | 5/13/2015 | 5/13/2015 | 5/13/2015 | A | PART |
Bob Reichert
|
|
|
Final inspection IL 3rd floor area C rooms C301-C310. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok except balconies
|
Electrical Rough-In | 5/12/2015 | 5/12/2015 | 5/12/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in IL area E 2nd floor corridor hard lid E251. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Final | 5/9/2015 | 5/11/2015 | 5/11/2015 | P | PART |
Bob Reichert
|
|
|
Final electrical inspection IL 1st floor area C rooms C105, C106, C107, C108, C109, and C110. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rooms listed ok final
|
Final | 5/7/2015 | 5/7/2015 | 5/7/2015 | P | PART |
Bob Reichert
|
|
|
Final inspection IL 1st floor area C rooms C102, C103, C104. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok final these rooms only
|
Electrical Rough-In | 5/5/2015 | 5/6/2015 | 5/6/2015 | A | PASS |
Bob Reichert
|
|
|
Rough in C Entry Canopy lights and receptacles. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/28/2015 | 4/28/2015 | 4/28/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection IL area E 3rd floor hard lid portions of Corridor 351. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/22/2015 | 4/23/2015 | 4/23/2015 | A | PASS |
Bob Reichert
|
|
|
Rough in T grid ceiling inspection IL 1st and 2nd floor area C Corridors C151, C152, C251, and C252. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/20/2015 | 4/21/2015 | 4/21/2015 | A | PASS |
Bob Reichert
|
|
|
Rough in inspection IL area C garage Elevator Lobby room PC5 walls and ceiling. Building permit number BLD13-00182. Call Lonny when onsite. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/10/2015 | 4/13/2015 | 4/13/2015 | P | PASS |
Bob Reichert
|
|
|
Re-inspection of low voltage cable in T grid ceiling D Commons rooms 103 and 127. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum corrections made, ok cover as requested
|
Electrical Rough-In | 4/9/2015 | 4/9/2015 | 4/9/2015 | P | PART |
Bob Reichert
|
|
|
Rough in T grid ceiling inspection rooms 103-150 D Commons. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum met contractor, left correction notice, NEC 300.11 cables and raceways shall not be supported by ceiling grids in rooms 103 and 127, rest of ceiling ok cover as requested
|
Electrical Rough-In | 4/7/2015 | 4/7/2015 | 4/7/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in hard lid ceiling inspection IL area D 2nd floor corridors and room: D251, D252, and D254. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/6/2015 | 4/6/2015 | 4/6/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection stairwell E. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/1/2015 | 4/1/2015 | 4/1/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection IL area E 1st floor ceiling soffit rooms E101-E106, E108, and E110. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 3/23/2015 | 3/24/2015 | 3/24/2015 | A | PASS |
Bob Reichert
|
|
|
Electrical rough in ceiling inspection IL area C 3rd floor corridors C351 and C352 T grid. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover ceiling as requested
|
Electrical Rough-In | 3/4/2015 | 3/4/2015 | 3/4/2015 | P | PASS |
Bob Reichert
|
|
|
Rough-in inspection IL building area E 3rd floor soffits rooms E301-E306, E308, and E310. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 3/2/2015 | 3/2/2015 | 3/2/2015 | P | PASS |
Bob Reichert
|
|
|
Rough-in IL area ''C'' 1st floor hard lid ceilings rooms: C151-C154, C156, C157, and C158. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 2/25/2015 | 2/26/2015 | 2/26/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection IL 2nd floor area D for hard lid soffits in rooms D201-D204, D206 and D208. Rough in inspection wall and ceiling for room D253 Lounge. Building permit BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 2/18/2015 | 2/18/2015 | 2/18/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection hard lid ceilings ''D'' Commons rooms: 116 ; 117. IL area ''E'' corridor and support room walls rooms: E151, E152, E153, E154,E155, E251, E252, E253, E254,E255 E351, E352, E353, ; E354,E355 Building permit # BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover as noted
|
Electrical Rough-In | 2/17/2015 | 2/17/2015 | 2/17/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection ''D'' Commons hard lid ceilings: corridor 123 ; 149 ; rooms: 123, 127, 128, 129, 130, 131, 132. IL hard lid ceilings area ''C'' 2nd floor: C251, C252, C253, C254, C256, C257, ; C258. Building permit # BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baumrough-in ok cover as noted
|
Electrical Rough-In | 2/11/2015 | 2/11/2015 | 2/11/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in ceiling and soffits in IL area ''D'' Commons rooms: 102, 115, 118, 119, 120, 121, 124, 126, 127, ; 128. Building permit # BLD13-00182. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover
|
Permanent Service | 2/11/2015 | 2/11/2015 | 2/11/2015 | P | PASS |
Daryl DeGrange
|
|
|
IL building ''C'' electrical room PC4 permanent service inspection. Building permit # BLD13-00182. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum p/s u/g n ok
|
Electrical Rough-In | 2/6/2015 | 2/6/2015 | 2/6/2015 | P | PASS |
Daryl DeGrange
|
|
|
Re-inspection bathrooms 151; 152 and Corridor 110 in ''D'' Commons area. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in area to be inspected completed, rough-in ok cover
|
Electrical Rough-In | 2/3/2015 | 2/4/2015 | 2/4/2015 | A | PART |
Daryl DeGrange
|
|
|
Rough-in hard lid ceilings ''D'' Commons rooms: 106, 111, Corridor 110, 151, ; 152. Building permit # BLD13-00182. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum Partial r/i ok cover corredor ceilings,No cover for bathroom ceilings, exhaust fans not installed or on site.
|
Electrical Rough-In | 1/29/2015 | 1/30/2015 | 1/30/2015 | P | PASS |
Rock A. Hudson
|
|
|
Wall rough-in inspection for IL area ''D'' garage rooms: PD5 Resident Storage and PD6 Storage. Building permit number BLD13-00182. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum Storage rooms as described in basement wall rough in ok cover
|
Electrical Rough-In | 1/27/2015 | 1/27/2015 | 1/27/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection ceiling hard lid for IL area ''C'' 3rd floor corridors: C351, C352 ; rooms: C353, C354, C356, C357, ; C358. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum Rough-in ok cover hard lid areas as per
|
Electrical Rough-In | 12/24/2014 | 12/29/2014 | 12/29/2014 | P | PASS |
Bob Reichert
|
|
|
Rough-in IL 3rd floor area "E" rooms: E301-E306, E308, ; E310. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 12/23/2014 | 12/24/2014 | 12/24/2014 | A | PASS |
Bob Reichert
|
|
|
Rough-in IL 2nd floor area "E" rooms: E201-E206, E208, ; E210. Rough-in Commons 1st floor area "D" rooms: 101, 102, 115, 117-128, 131, 132, ; 149. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 12/23/2014 | 12/23/2014 | 12/23/2014 | P | PASS |
Bob Reichert
|
|
|
Rough-in for IL 1st floor area "E" rooms: E101-E106, E108, ; E110. Call Lonny when on site. Thanks, Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 12/20/2014 | 12/22/2014 | 12/22/2014 | P | PASS |
Bob Reichert
|
|
|
Electrical rough-in IL 2nd floor area "D" rooms: D251-D256 ; D258. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Conference | 12/19/2014 | 12/19/2014 | 12/19/2014 | P | DONE |
Bob Reichert
|
|
|
Conference on receptacles in living units. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum talked about receptacles in bedroom, wrote correction notice, NEC 310.21(B)(3) shall use maximum 15A receptacle on 15A circuit
|
Electrical Rough-In | 12/16/2014 | 12/17/2014 | 12/17/2014 | P | PASS |
Bob Reichert
|
|
|
Electrical rough-in for "D" Commons rooms: 103-111, 114, 151, ; 152 and ceiling soffit inspection for IL 1st floor area "C" rooms: C101 - C110. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 12/16/2014 | 12/16/2014 | 12/16/2014 | P | PASS |
Bob Reichert
|
|
|
IL Building area "D" 2nd floor rooms: D201, D202, D203, D204, D206, ; D208 rough-in inspection. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri ok per request
|
Electrical Rough-In | 12/9/2014 | 12/9/2014 | 12/9/2014 | P | PASS |
Bob Reichert
|
|
|
Rough-in ceiling inspection IL building area "E" 2nd floor corridor E251 ; 3rd floor corridor E351. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover upper level ceiling as requested
|
Electrical Rough-In | 11/25/2014 | 11/26/2014 | 11/27/2014 | P | PASS |
Bob Reichert
|
|
|
Electrical rough-in for IL area "C" 2nd floor rooms: C201, C202, C203, C204, C205, C206, C207, C208, C209, ; C210. Rough-in IL area "E" ceiling only Corridor E151. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum soffits as requested and corridor ceiling ok cover
|
Electrical Rough-In | 11/3/2014 | 11/4/2014 | 11/4/2014 | A | PASS |
Bob Reichert
|
|
|
Rough-in inspection for IL area "C" electrical rooms: C155, C255, ; C355. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri ok as noted
|
Electrical Rough-In | 10/30/2014 | 10/31/2014 | 10/31/2014 | A | CANC |
Bob Reichert
|
|
|
see response for 10/30/14
|
Electrical Rough-In | 10/30/2014 | 10/30/2014 | 10/31/2014 | P | PASS |
Bob Reichert
|
|
|
Electrical rough-in for drop ceiling in IL 3rd floor area "C" rooms: C301, C302, C303, C304, C305, ; C306. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri ok as requested
|
Electrical Rough-In | 10/28/2014 | 10/29/2014 | 10/29/2014 | A | PASS |
Bob Reichert
|
|
|
Rough-in inspection area "C" IL rooms: C107, C108, C109, C110, misc support rooms C153, C154, C156, C157, C158, and stairwells "C1" ; "C2". Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 10/27/2014 | 10/28/2014 | 10/28/2014 | A | PASS |
Bob Reichert
|
|
|
Rough-in inspection IL rooms: C101, C102, C103, C104, C105, C106, and corridor C151. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri ok as requested
|
Electrical Rough-In | 10/23/2014 | 10/24/2014 | 10/24/2014 | P | PASS |
Bob Reichert
|
|
|
Drop hard lid ceilings in C307, C308, C309, ; C310 bathrooms and short corridor need light fixture install inspection. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum hard lids ok as requested
|
Conference | 10/20/2014 | 10/21/2014 | 10/21/2014 | A | DONE |
Bob Reichert
|
|
|
Conference discussion on hallways, Country Home garages, and Skilled Nursing headwalls. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum met 445 and contractor, they will fix pipes under panel, ok on head wall, will protect wiring in garages, 445 will advise for halls
|
Electrical Rough-In | 10/14/2014 | 10/15/2014 | 10/15/2014 | A | PASS |
Bob Reichert
|
|
|
Electrical rough-in for IL 1st floor area "C" rooms: C107, C108, C109, C110, ; Housekeeping C157. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri rooms as listed ok cover
|
Electrical Rough-In | 10/2/2014 | 10/3/2014 | 10/3/2014 | P | PASS |
Bob Reichert
|
|
|
Electrical rough-in for IL building 2nd floor rooms: C201, C202, C203, C204, C205, C206, C207, C208,C209, C210, and Corridors C251, C252, ; C253. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri ok per requested list
|
Electrical Rough-In | 9/15/2014 | 9/16/2014 | 9/16/2014 | A | PASS |
Bob Reichert
|
|
|
Electrical rough-in IL building area "C" 3rd floor rooms: C301, C302, C303, ; C304. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri ok as requested
|
Electrical Rough-In | 9/11/2014 | 9/11/2014 | 9/11/2014 | P | PASS |
Bob Reichert
|
|
|
Rough-in inspection IL building area "C" rooms- C305, C306, C307, Corridor C352, ; Lobby C353. Call Lonny when on site to escort to inspection area. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri ok per description
|
Electrical Rough-In | 9/9/2014 | 9/9/2014 | 9/9/2014 | P | PASS |
Bob Reichert
|
|
|
Need electrical rough-in for IL wing "C" rooms C308, C309, ; C310. Call Lonny when on site to escort to inspection rooms. Thanks Phone #: ###-#### Inspection requested via web by Lonny Baum c 308,09,10 ri ok
|
Electrical Rough-In | 8/22/2014 | 8/25/2014 | 8/25/2014 | A | PASS |
Rex Boyles
|
|
|
Wall rough-in 3rd floor IL corridor area "C". Call Lonny when on site. Thanks Phone #: ###-#### Inspection requested via web by Lonny Baum 1st 2foot of ceiling corridor 3rd floor area C r/i ok
|
Conference | 8/19/2014 | 8/20/2014 | 8/20/2014 | A | DONE |
Bob Reichert
|
|
|
Conference with Petra on sheet rocking areas that have not been electrically roughed in. Call Lonny when on site. Thanks, Lonny Phone #: ###-#### >> Inspection requested via web by Lonny Baum talked about issue stop work unless general stops covering up electricians area to work in, contractors agreed to fix their scheduling for construction
|
Electrical Rough-In | 8/15/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Bob Reichert
|
|
|
Corridor rough-in ceiling inspection for 1st floor Independent Living areas A & B. Call Lonny when on site to escort to inspection area. Thanks Phone #: ###-#### >> Inspection requested via web by Lonny Baum ok for ceiling A&B
|
Electrical Rough-In | 8/13/2014 | 8/14/2014 | 8/14/2014 | A | NH |
Bob Reichert
|
|
|
Need rough-in inspection for Independent Living 1st floor corridor ceiling area A & B. Call Fabian @ ###-#### when on site to escort to inspection area. Thanks. Phone #: ###-#### >> Inspection requested via web by Lonny Baum called several times, looked for truck, left messages, shall recall
|
Electrical Rough-In | 8/6/2014 | 8/7/2014 | 8/7/2014 | A | PART |
Bob Reichert
|
|
|
Electrical rough-in inspection of C-wing corridor for cover. Call when on site to escort to building. Thanks, Lonny Phone #: ###-#### >> Inspection requested via web by Lonny Baum ok cover corridor ceiling part K,L for C-wing only
|