Final | 9/25/2015 | 9/28/2015 | 9/28/2015 | A | PASS |
Rock A. Hudson
|
|
|
Final for occupancy for Skilled Nursing Building J Contact Brandon Keating @ ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
|
Final | 9/18/2015 | 9/21/2015 | 9/21/2015 | P | PART |
Bob Reichert
|
|
|
Skilled Nursing Bldg J Final Contact Craig Timmons Phone #: ###-#### Inspection requested via web by Cathy Duchek ok except for counters, lights to be fitted
|
Permanent Service | 5/21/2015 | 5/21/2015 | 5/21/2015 | P | PASS |
Bob Reichert
|
|
|
Permanent service inspection SNF J. Building permit number BLD13-00189. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum will check fault current sticker later, p/s u/g n ok
|
Electrical Rough-In | 5/14/2015 | 5/14/2015 | 5/14/2015 | A | PASS |
Bob Reichert
|
|
|
Rough in inspection all ceiling hard lid areas in SNF building J. Building permit number BLD13-00189. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested, left correction notice NEC for all site locations, 110.26(F)(1) there shall be no foreign systems over panels such as J132
|
Electrical Rough-In | 3/4/2015 | 3/4/2015 | 3/4/2015 | P | PASS |
Bob Reichert
|
|
|
Rough-in inspection SNF J Spa room J108 and adjoining bathroom J109. Building permit number BLD13-00189. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 2/13/2015 | 2/17/2015 | 2/17/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection SNF ''J'' all remaining walls101,102,103,104,105,106,107,110,111,112,113,114,115,117,118,119,120,122,123,124,125, 126,127,128,131,132,133,134,135 except Spa Room J108,j109. Building permit number BLD13-00189. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover as noted
|
Electrical Rough-In | 2/10/2015 | 2/10/2015 | 2/10/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection SNF ''J'' patient rooms: J01-J16, rooms only. BLDG permit # BLD13-00189. Call Lonny when on-site. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover as identified
|
Electrical Rough-In | 1/27/2015 | 1/27/2015 | 1/27/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection Skilled Nursing ''J'' upper hard lid ceiling so sheet rock can be installed. All rooms except Spa Room J108. Call Lonny when on site. Thanks. BLD13-00189. Phone #: ###-#### Inspection requested via web by Lonny Baum Rough-in ok cover hard lid as per stated
|
Conference | 1/23/2015 | 1/23/2015 | 1/23/2015 | P | DONE |
Daryl DeGrange
|
|
|
Conference on previously issued correction notice dated 12-9-14 concerning Spa Room J108. Have reply from electrical engineer. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum Discussed exception 680.44(D)(5) for luminaires and receptacles less than 5 ft. from motorized tub, Bonding,GFCI protection, 680.43(B)(2) Non conductive luminaires,680.12 Panic button
|
Conference | 12/9/2014 | 12/9/2014 | 12/9/2014 | P | DONE |
Bob Reichert
|
|
|
Skilled Nursing building "J" conference on Spa room J108. Call Lonny when on-site. Phone #: ###-#### Inspection requested via web by Lonny Baum talked about and looked at spa area, wrote correction notice,NEC 680.43(A) receptacles shall be at least 6' from inside walls of spa, and be gfci protected, 680.43(B) luminaires shall be gfci protected if less than 7'-6" from spa, shall have glass or plastic globe and be suitable for use in a damp location, 680.43(C) switches shall be at least 5' from inside walls of spa
|
Electrical Rough-In | 11/7/2014 | 11/10/2014 | 11/10/2014 | A | PASS |
Bob Reichert
|
|
|
Electrical rough-in for electrical room exterior wall in room J125. Call Lonny when on-site. Thanks Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover exterior walls
|
Rough-In Permanent Service | 7/24/2014 | 7/24/2014 | 7/24/2014 | P | PASS |
Rock A. Hudson
|
|
|
Skilled Nursing building "J". Need service, UFER, and slab-on-grade inspection. Call Lonny when on site to escort to inspection area. Thanks. Phone #: ###-#### >> Inspection requested via web by Lonny Baum Concrete encased, electrical rm, all under ground for building common areas under slab rough in ok cover. No permenant service inspection
|