Final | 9/30/2014 | 10/1/2014 | 10/1/2014 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn final ok
|
Final | 9/4/2014 | 9/5/2014 | 9/5/2014 | A | CANC |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn
|
Rough-In Permanent Service | 8/8/2014 | 8/8/2014 | 8/8/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough-in p/s u/g n ok
|
Rough-In Permanent Service | 8/7/2014 | 8/7/2014 | 8/7/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn NEC 300. 4 Nail plate NEC 320.23 Guard strips for NM cables crossing over trusses witin 6 ft. of attic accesses NEC 312.3 combustible material boxes shall be set flush with the finished surface,
|