Final | 3/4/2015 | 3/5/2015 | 3/5/2015 | A | PASS |
Daryl DeGrange
|
|
|
Rocky Phone #: ###-#### correction done, final ok
|
Final | 3/3/2015 | 3/3/2015 | 3/3/2015 | P | FAIL |
Cevyn Recla
|
|
|
Rocky Phone #: ###-#### Rocky was on site, 422.31 Disconnecting means required for permanently installed applliances, Hood, D/W, H2O Heater 410.16 B, Luminaires in clothes closet, open lamp fixtures not permitted 422.11 a overcurrent shall not exceed marking of appliance, AC X2 250.94 Intersystem bonding connectioin required for other systems, bond bar for utilities. 408.4 Circuit directory required
|
Electrical Rough-In | 8/13/2014 | 8/13/2014 | 8/13/2014 | P | PASS |
Rex Boyles
|
|
|
Rocky Phone #: ###-#### r/i ok
|
Permanent Service | 7/15/2014 | 7/16/2014 | 7/16/2014 | A | PASS |
Rex Boyles
|
|
|
Rocky Phone #: ###-#### p/s u/g n ok
|