Final | 5/12/2015 | 5/13/2015 | 5/13/2015 | A | PASS |
Daryl DeGrange
|
|
|
Please Call Matt ###-#### 1/2 prior to arrival. Phone #: ###-#### Inspection requested via web by Buster Bowen Job complete, final ok
|
Final | 4/6/2015 | 4/7/2015 | 4/7/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Matt Foster is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen NEC 334.12(B)(4) NM shall not be installed in wet or damp locations, wiring for mini split systems.
|
Electrical Rough-In | 9/23/2014 | 9/24/2014 | 9/24/2014 | A | PASS |
Rex Boyles
|
|
|
Matt. Bottom apartment dryer circuit. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i ok unit C dryer outlet
|
Electrical Rough-In | 8/27/2014 | 8/28/2014 | 8/28/2014 | P | PASS |
Rex Boyles
|
|
|
Matt. Can you call half hour prior to heading towards site. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i ok for water heater circuit and washer dryer circuits and mini split power and controls for units A,B,C and D also remove bonding screws in loadcenters before final insp.
|
Electrical Rough-In | 8/11/2014 | 8/12/2014 | 8/12/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Matt. Phone #: ###-#### Inspection requested via web by Sean DeLacy NEC 230.24(A) ex3 Clearance of 18in. of service conductors above overhang portion of roof NEC 240.24(D) (Service panel) Over current devices shall not be located in the vcinity of easily ignitible material, such as clothes closets, BCC 04-05-31 A panel location shall not be installed in a unsafe location
|