Final | 9/12/2014 | 9/12/2014 | 9/12/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters final ok
|
Final | 9/11/2014 | 9/11/2014 | 9/11/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters 210.8(B)(5) Sinks — where receptacles are installed within 1.8 m (6 ft) of the outside edge of the sink they shall have GFCI protection 517.18 (B)- General Care Areas All receptacles shall be listed “hospital grade” and shall be so identified.
|
Electrical Rough-In | 8/14/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Rock A. Hudson
|
|
|
ceiling inspection please Phone #: ###-#### Inspection requested via web by Celinda Winters Grid rough in ok cover
|
Electrical Rough-In | 7/28/2014 | 7/29/2014 | 7/29/2014 | P | PASS |
Rock A. Hudson
|
|
|
Partial Rough-in: Wall with panel and bathroom ceiling Phone #: ###-#### >> Inspection requested via web by Celinda Winters Bathroom hard lid and panel wall rough in ok cover
|
Electrical Rough-In | 7/18/2014 | 7/21/2014 | 7/21/2014 | A | PASS |
Rex Boyles
|
|
|
Wall rough-in Phone #: ###-#### >> Inspection requested via web by Celinda Winters r/i walls ok
|