Final | 9/29/2014 | 9/29/2014 | 9/29/2014 | P | PASS |
Daryl DeGrange
|
|
|
Key is on top of meter main at back of house for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov correction done, final ok
|
Final | 9/25/2014 | 9/25/2014 | 9/26/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Key is on top of meter main at back of the house for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov NEC 334.12 (B)(4) NM cable not permited in wet or damp locations underground to unattached garage
|
Final | 9/23/2014 | 9/24/2014 | 9/24/2014 | A | FAIL |
Bob Reichert
|
|
|
Key is on top of meter main back of the house for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov called, left correction notice, NEC 110 shall install devices per instructions, 4-way switches top stairs, hall, pantry gfci shall operate, shall protect grounding electrode conductor
|
Electrical Rough-In | 7/28/2014 | 7/29/2014 | 7/29/2014 | A | PASS |
Daryl DeGrange
|
|
|
Trench inspection from house to detached garage Phone #: ###-#### >> Inspection requested via web by daniel bibikov Rough-in ok cover trench PVC at 13 in.GFCI required
|
Rough-In Permanent Service | 7/23/2014 | 7/24/2014 | 7/24/2014 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov correction done, rough-in p/s u/g n ok w/detacted garage, no underground (230.79)
|
Rough-In Permanent Service | 7/23/2014 | 7/23/2014 | 7/23/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov B.C.C 04-05-23 Unlawful to conceal It shall be unlawful for any person to cover up or in any way conceal any electrical wiring, cables, conduits or other equipment until the same has been inspected and approved by an electrical inspector
|