Final | 8/18/2014 | 8/19/2014 | 8/19/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears Final ok
|
Rough-In Permanent Service | 8/11/2014 | 8/11/2014 | 8/11/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears Unit 49 rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 8/7/2014 | 8/8/2014 | 8/8/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears 250.53(D)(2)- When rod is used for grounding electrode system for permenant service supplemental rod required. 330.30- MC cable shall be supported at inervals not exceeding 6'
|
Electrical Rough-In | 7/22/2014 | 7/23/2014 | 7/23/2014 | A | PASS |
Rock A. Hudson
|
|
|
underground trench inspection Phone #: ###-#### >> Inspection requested via web by Seth Stears Under ground fire and security low volt conduit rough in ok cover
|