Final | 1/26/2015 | 1/26/2015 | 1/26/2015 | P | PASS |
Cevyn Recla
|
|
|
Mucho Phone #: ###-####
BLD INP 415 to verify 2 hour rating for soffit cans, no record of inspection.
Final OK
|
Permanent Service | 9/30/2014 | 9/30/2014 | 9/30/2014 | P | PASS |
Rex Boyles
|
|
|
Mucho Phone #: ###-#### corrections made p/s u/g n ok
|
Rough-In Permanent Service | 9/24/2014 | 9/25/2014 | 9/25/2014 | A | FAIL |
Rex Boyles
|
|
|
Mucho Phone #: ###-#### 110.26(A)(2)- Width of working space needs to be 30 inches minimum around meter base. 250.52(A)(3)(2) A concrete encased electrode consist of at least 20 foot of steel in direct contact with earth. stemwall not acceptable (see info note). 3 inch secondary from ID.Power too croocked for locknut and terminal connector to be installed properly. Suggest bringing meter base out until 3 inch conduit is straight.
|
Electrical Rough-In | 9/25/2014 | 9/25/2014 | 9/25/2014 | P | PASS |
Rex Boyles
|
|
|
Mucho Phone #: ###-#### r/i ok can light in soffit needs 2 hr encapsulation
|