Final | 1/29/2015 | 1/29/2015 | 1/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Corrections made Final ok
|
Final | 1/29/2015 | 1/29/2015 | 1/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
Corrections made. Final ok
|
Final | 1/27/2015 | 1/28/2015 | 1/28/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Jason Phone #: ###-#### 110.24- Available fault current shall be posted on service gear. 314.25- All baxes and conduit bodies shall have covers. 422.30- Water heater disconnect handle shall be less than 6' 7" max. * Unable to test detail area due to taped off for paint. * Other electrical permits need finalled for occupancy.
|
Final | 1/21/2015 | 1/21/2015 | 1/21/2015 | P | PART |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Request for temp final for office area so items could be brought in. Offices temp final ok. Check for GFCI protection for drinking fountain
|
Electrical Rough-In | 1/16/2015 | 1/16/2015 | 1/16/2015 | P | PASS |
Rock A. Hudson
|
|
|
ceiling - Mike (bldg super) Phone #: ###-#### Office area grid rough in ok cover
|
Electrical Rough-In | 12/29/2014 | 12/29/2014 | 12/29/2014 | P | PASS |
Rock A. Hudson
|
|
|
Mike-CEILING Phone #: ###-#### Canopy ceiling rough in ok cover
|
Electrical Rough-In | 12/22/2014 | 12/22/2014 | 12/22/2014 | P | PASS |
Rock A. Hudson
|
|
|
eletrical service via phone with jason 12-22-14 blh// Mike Phone #: ###-#### Office walls and bath hard lids rough in ok cover
|
Permanent Service | 12/22/2014 | 12/22/2014 | 12/22/2014 | P | PASS |
Rock A. Hudson
|
|
|
eletrical service via phone with jason 12-22-14 blh// Mike Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 12/11/2014 | 12/12/2014 | 12/12/2014 | A | PART |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Bathroom wall only rough in ok cover
|
Electrical Rough-In | 10/13/2014 | 10/13/2014 | 10/13/2014 | P | PASS |
Rock A. Hudson
|
|
|
Mike-underground Phone #: ###-#### Service entrance conduits rough in ok cover
|
Electrical Rough-In | 10/6/2014 | 10/8/2014 | 10/8/2014 | A | PASS |
Rock A. Hudson
|
|
|
underground - Mike Phone #: ###-#### Service entrance conduit from service location 50' to west. To allow a section to be covered for access and inspect transformer location to east next. Rough in ok cover
|
Electrical Rough-In | 9/23/2014 | 9/24/2014 | 9/24/2014 | A | PASS |
Bob Reichert
|
|
|
Mike Phone #: ###-#### u/g ok south parking lot lighting
|
Electrical Rough-In | 8/29/2014 | 9/2/2014 | 9/2/2014 | A | PART |
Rock A. Hudson
|
|
|
Underground conduits - Mike Phone #: ###-#### 1st run of under ground to feed existing light poles on lot. 4 runs north side of foundation. Runs later will call to discuss with Daryl on how much of U/G he wants to see. 4 runs east to west along north foundation rough in ok cover
|
Electrical Rough-In | 8/19/2014 | 8/19/2014 | 8/19/2014 | P | PASS |
Daryl DeGrange
|
|
|
uffer underground - Jason Phone #: ###-#### Rough-in ok cover concrete encased electrode
|