Final | 9/4/2014 | 9/5/2014 | 9/5/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Dave Brueggemann Final ok
|
Electrical Rough-In | 8/6/2014 | 8/6/2014 | 8/6/2014 | P | PASS |
Rock A. Hudson
|
|
|
Sean Phone #: ###-#### Rough in ok cover
|
Permanent Service | 8/6/2014 | 8/6/2014 | 8/6/2014 | P | PASS |
Rock A. Hudson
|
|
|
Sean Phone #: ###-#### Unit S-2 p/s u/g rec ok
|
Electrical Rough-In | 8/1/2014 | 8/4/2014 | 8/4/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Apt s2 - Shawn Phone #: ###-#### 334.30- NM cable shall be secured with in 12" of boxes with clamps. NM cable shall be supported at intervals not exeeding 4 1/2' max. 300.4- Where NM cable passed through bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. 424.93(A)(3)- Receptical outlet locations shall clear edge of baseboard heater by 8" minimum. BBC 4-05-32- Code violations not to be retained
|