Final | 4/9/2015 | 4/9/2015 | 4/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Final ok
|
Final | 3/16/2015 | 3/16/2015 | 3/16/2015 | P | PART |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Label panels, 1 x-ray room equipment, roof yet for finish. Temp final ok
|
Electrical Rough-In | 3/2/2015 | 3/3/2015 | 3/3/2015 | A | PASS |
Rex Boyles
|
|
|
Mike Phone #: ###-#### r/i front column exterior sconce relocation and reception millwork ok to cover
|
Electrical Rough-In | 2/24/2015 | 2/25/2015 | 2/25/2015 | A | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### 8 Fixtures damaged during shipping,4 x-ray and 4 corridor. Contractor will be on site in future with ladder. Corridor, x-ray rooms, and front reception areas grid rough in ok cover
|
Electrical Rough-In | 2/17/2015 | 2/18/2015 | 2/18/2015 | A | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Grid rough in N.E. and S.E. corner offices and corridors E. and W. of x-ray rooms. Rooms 107, 108, 109, 111, 116, 118, 119, 123, 156. Grid rough in as noted ok cover
|
Electrical Rough-In | 2/9/2015 | 2/10/2015 | 2/10/2015 | A | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### West back grid rough in ok cover
|
Permanent Service | 2/9/2015 | 2/10/2015 | 2/10/2015 | A | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Arc fault current capacity confirmed. p/s u/g n ok
|
Electrical Rough-In | 2/6/2015 | 2/6/2015 | 2/6/2015 | P | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Grid in exam rooms and exam corridors rough in ok cover
|
Electrical Rough-In | 1/27/2015 | 1/27/2015 | 1/27/2015 | P | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Front canopy lid and reception area wall rough in ok cover
|
Electrical Rough-In | 1/22/2015 | 1/22/2015 | 1/22/2015 | P | CANC |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### 1/2 walls each side of foyer rough in ok cover
|
Electrical Rough-In | 1/14/2015 | 1/14/2015 | 1/14/2015 | P | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Interior foyer, x-ray rooms and nurse call stations walls rough in ok cover
|
Electrical Rough-In | 1/5/2015 | 1/6/2015 | 1/6/2015 | A | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Walls and hard lids south of dividing corridor except entry area. Ok to one side x-ray area if contractor wants to allow. Rough in ok cover
|
Electrical Rough-In | 12/15/2014 | 12/15/2014 | 12/15/2014 | P | PASS |
Rex Boyles
|
|
|
Mike Phone #: ###-#### r/i ok other side of walls in electric room and janitor/fire sprinkeler riser room
|
Electrical Rough-In | 12/10/2014 | 12/10/2014 | 12/10/2014 | P | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Electrical room, Janitor closet, and fire riser room 1 side only rough in ok cover
|
Electrical Rough-In | 12/3/2014 | 12/3/2014 | 12/3/2014 | P | PASS |
Rex Boyles
|
|
|
Mike Phone #: ###-#### r/i ok exterior walls only east half of bldg.
|
Electrical Rough-In | 11/25/2014 | 11/26/2014 | 11/26/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### South entrance rough in ok cover
|
Electrical Rough-In | 11/25/2014 | 11/25/2014 | 11/25/2014 | P | FAIL |
Rock A. Hudson
|
|
|
mike Phone #: ###-#### 330.10- MC cable shall not be installed where subject to physical damage. Ballasts for recessed cans shall be installed in a manner that allows access for servicing.
|
Electrical Rough-In | 11/19/2014 | 11/19/2014 | 11/19/2014 | P | PART |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### From center north/south corridor to west interior walls rough in ok cover
|
Electrical Rough-In | 11/17/2014 | 11/17/2014 | 11/17/2014 | P | PART |
Rock A. Hudson
|
|
|
mike Phone #: ###-#### From center north/south corridor to west outer perimeter walls only rough in ok cover
|
Electrical Rough-In | 11/4/2014 | 11/5/2014 | 11/5/2014 | A | PART |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Upper parapet wall rough in ok cover
|
Electrical Rough-In | 10/31/2014 | 10/31/2014 | 10/31/2014 | P | PASS |
Cevyn Recla
|
|
|
Mike Phone #: ###-#### West end of building, rooftop outlets OK to cover
|
Electrical Rough-In | 9/29/2014 | 9/29/2014 | 9/29/2014 | P | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### 7 pole bases rough in ok cover
|
Electrical Rough-In | 9/15/2014 | 9/15/2014 | 9/15/2014 | P | PASS |
Rock A. Hudson
|
|
|
Underground - Mike Phone #: ###-#### Floor boxes, fiber conduits, sign conduits rough in ok cover
|
Electrical Rough-In | 9/10/2014 | 9/11/2014 | 9/11/2014 | P | PART |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### East lot, south west lot, in building, communication conduits, west to nurses station, S. E. corner underground rough in ok cover
|
Electrical Rough-In | 8/13/2014 | 8/14/2014 | 8/14/2014 | A | PASS |
Rock A. Hudson
|
|
|
Daryl-ufer ground Phone #: ###-#### 3/0 used rough in ok cover
|