Final | 11/10/2014 | 11/12/2014 | 11/12/2014 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan King Corrections made, Permanent service for solar OK
|
Final | 11/4/2014 | 11/5/2014 | 11/5/2014 | P | FAIL |
Cevyn Recla
|
|
|
36 solar panels. AC micro-inverter system. No DC voltage. We used Enphase M250 micro inverters and ET Solar solar panels, both listed and approved. This is a pole mount system, mounted back behind the house. There is a single home run, in conduit, running 300 feet from the solar array to the knife switch, located next to meter base on south corner of home. From the knife switch to the 40 amp breaker in main panel, at the top, opposite the feeder lugs. The solar breaker is clearly marked with label plate, and its circuit number identified in the knife switch and the panel schedule. The inverters, panels and rails are all bonded with a number 6 ground that is bonded to one of the 6" poles that runs 8 feet deep into the ground. The equipment/circuit ground is a number 6 in the conduit that runs back to the service ground.
For access to the garage/main panel, call home owner at 208.867.8002. His name is Dwayne Peters.
Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King No underground inspection performed 352.30 Securing and support of riser 250.92B.4 bond bushings at concentric knockouts 250.96 non conductive paint to be removed at ground point 240.15B circuit breakers shall open all ungrounded conductors simultaneously no supplemental ground Spoke to Jason Blais, 11-5-14, 2:30 PM, no building permit required
|
Rough-In Permanent Service | 11/5/2014 | 11/5/2014 | 11/5/2014 | A | CANC |
Cevyn Recla
|
|
|
wrong insp.
|