Final | 12/2/2014 | 12/2/2014 | 12/2/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS Door separates elevator disconnecting means from bathroom. No card posted. Final ok
|
Final | 12/1/2014 | 12/1/2014 | 12/1/2014 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS called, left correction notice, BCC 4-05-31(A) shall not install disconnects in bathroom, NEC 210.8(B)(2) kitchen receptacles shall be gfci protected, 422.51 vending machines shall be gfci protected, Note: shall close open box ceiling 3rd floor
|
Electrical Rough-In | 9/22/2014 | 9/23/2014 | 9/23/2014 | P | PASS |
Daryl DeGrange
|
|
|
Inspect 3rd floor and Stairs - Call Eric Story ###-#### Phone #: ###-#### Inspection requested via web by ERIC CENTERS rough-in ok cover
|
Rough-In Permanent Service | 9/10/2014 | 9/12/2014 | 9/12/2014 | A | PASS |
Daryl DeGrange
|
|
|
please inspect 2nd floor and building service. Phone #: ###-#### Inspection requested via web by ERIC rough-in p/s u/g n ok
|
Electrical Rough-In | 9/8/2014 | 9/9/2014 | 9/9/2014 | A | PASS |
Daryl DeGrange
|
|
|
Please inspect exterior patios for cover. Phone #: ###-#### Inspection requested via web by ERIC CENTERS rough-in ok cover 2nd floor patios
|
Electrical Rough-In | 9/3/2014 | 9/4/2014 | 9/4/2014 | A | PART |
Daryl DeGrange
|
|
|
Please inspect first floor only. Phone #: ###-#### Inspection requested via web by ERIC CENTERS Rough-in ok cover first floor minus stairwells
|