Final | 11/17/2014 | 11/18/2014 | 11/18/2014 | P | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson corrections made final ok
|
Final | 11/17/2014 | 11/17/2014 | 11/17/2014 | P | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson still missing extension rings could not leave a message, voicemail box was full
|
Final | 11/14/2014 | 11/14/2014 | 11/14/2014 | P | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Spoke to contractor 210.8.a.3 GFI required outdoor 210.8.a.2 GFI required garages 406.9.b.1 Receptacle in wet location, weatherproof enclosure required 314.20 extension rings required where boxes are recessed 422.31 disconecting means required on permanently installed appliances, micro and hood BCC Energy- 50% of lamps to be of energy efficient type
|
Electrical Rough-In | 8/26/2014 | 8/27/2014 | 8/27/2014 | A | CANC |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson needed r/i p/s
|
Rough-In Permanent Service | 8/27/2014 | 8/27/2014 | 8/27/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson ri ok p/s u/g n ok
|