Final | 10/29/2015 | 10/29/2015 | 10/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
Bldg F Floor 1,2,3 done 10-23-15 Floor 4 don 9-21-15, Bldg G Floor 1,2,3 done 10-27-15. Final ok
|
Electrical Rough-In | 10/26/2015 | 10/27/2015 | 10/27/2015 | A | PASS |
Daryl DeGrange
|
|
|
Partial Final, "G" Section, floors 1,2 and 3, all rooms and including corridors. Contact Bob Mott @###-#### or Craig Timmons @ ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek partial final ok
|
Final | 10/22/2015 | 10/23/2015 | 10/23/2015 | P | PART |
Daryl DeGrange
|
|
|
Final for F section floors 1,2, ; 3. All rooms including corridors. Only. Contact Bob Mott @ ###-#### or Craig Timmons @ ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek partial final ok
|
Electrical Rough-In | 10/8/2015 | 10/8/2015 | 10/8/2015 | P | PASS |
Daryl DeGrange
|
|
|
Ceiling Hall 1st Floor Area G for Tile Cover Contact Craig Timmons @ ###-#### or Bob Mott @###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek rough-in ok cover ceiling grid
|
Final | 9/29/2015 | 9/30/2015 | 9/30/2015 | P | PART |
Bob Reichert
|
|
|
2nd floor area F and 3rd floor area F **PARTIAL FINAL** // Bob Phone #: ###-#### ok as requested
|
Electrical Rough-In | 9/29/2015 | 9/30/2015 | 9/30/2015 | P | PASS |
Bob Reichert
|
|
|
Hall 2nd floor G and 3rd floor G // Bob Phone #: ###-#### ok cover as requested
|
Final | 9/18/2015 | 9/21/2015 | 9/21/2015 | P | PART |
Bob Reichert
|
|
|
F4 Final and F1 Dropped Ceiling Rough-In contact Craig Timmons ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek ok cover as requested, for final, shall inspect balconies
|
Electrical Rough-In | 9/9/2015 | 9/9/2015 | 9/9/2015 | P | PASS |
Bob Reichert
|
|
|
Ceiling Cover Area ''F'' 2nd floor corridors and 3rd floor corridors Contact Bob Mott @ ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek ok cover ceiling as requested
|
Electrical Rough-In | 8/27/2015 | 8/28/2015 | 8/28/2015 | P | PASS |
Bob Reichert
|
|
|
Main Area F, 4th Floor Hallway Ceiling Inspection Area F Contact Bob Mott Phone #: ###-#### Inspection requested via web by Cathy Duchek ok cover aa requested
|
Final | 8/12/2015 | 8/13/2015 | 8/13/2015 | P | CANC |
Bob Reichert
|
|
|
G 1st floor corridor ceiling hard lid G151 Phone #: ###-#### Inspection requested via web by Fabian Luna see ri for G151, not a final yet
|
Electrical Rough-In | 8/13/2015 | 8/13/2015 | 8/13/2015 | P | PASS |
Bob Reichert
|
|
|
ok cover G151 hard lid in G 1st floor
|
Electrical Rough-In | 8/10/2015 | 8/11/2015 | 8/11/2015 | P | PASS |
Bob Reichert
|
|
|
G SECOND FLOOR CORRIDOR HARD LID Phone #: ###-#### Inspection requested via web by Fabian Luna ok cover as requested
|
Electrical Rough-In | 8/6/2015 | 8/6/2015 | 8/6/2015 | P | PASS |
Bob Reichert
|
|
|
corridor G351 HARD LIDS Phone #: ###-#### Inspection requested via web by Fabian Luna ok cover as requested
|
Electrical Rough-In | 7/31/2015 | 7/31/2015 | 7/31/2015 | P | PASS |
Daryl DeGrange
|
|
|
ceiling rough in for corridor f151 Phone #: ###-#### Inspection requested via web by Fabian Luna rough-in ok cover
|
Electrical Rough-In | 7/29/2015 | 7/29/2015 | 7/29/2015 | P | PASS |
Bob Reichert
|
|
|
ceiling rough in corridor f252 Phone #: ###-#### Inspection requested via web by Fabian Luna ok cover as requested
|
Electrical Rough-In | 7/23/2015 | 7/23/2015 | 7/23/2015 | P | PASS |
Bob Reichert
|
|
|
corridor ceilings in ''F'' Phone #: ###-#### Inspection requested via web by Fabian Luna ok cover as requested
|
Electrical Rough-In | 7/15/2015 | 7/16/2015 | 7/16/2015 | P | PASS |
Bob Reichert
|
|
|
Ceiling inspection in corridor F351, Elevator Lobby F352, Toilet F356, Com room F355 Phone #: ###-#### Inspection requested via web by Fabian Luna ok cover as requested
|
Electrical Rough-In | 7/1/2015 | 7/6/2015 | 7/6/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough in hard lid inspection IL building area F 4th floor rooms F451, F452, F453, F454, F456. Building permit number BLD13-00187. Call Fabian when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover hard lid as noted
|
Electrical Rough-In | 6/25/2015 | 6/26/2015 | 6/26/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection IL area G 1st floor soffit rooms G101-G107. Building permit number BLD13-00187. Call Fabian when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Permanent Service | 6/22/2015 | 6/23/2015 | 6/23/2015 | A | PASS |
Bob Reichert
|
|
|
Permanent service inspection IL area G Garage room PG2 fed by Idaho Power transformer TB-20. Building permit number BLD13-00187. Call Fabian when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum p/s u/g n ok
|
Electrical Rough-In | 6/8/2015 | 6/8/2015 | 6/8/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in hard lid soffits IL 2nd floor area G rooms G201-G207. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 5/27/2015 | 5/27/2015 | 5/27/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in hard lid soffits rooms G301-G305. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 5/5/2015 | 5/5/2015 | 5/5/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough in inspection IL area F 1st floor soffit rooms F101 - F107, ; F109. Wall rough in IL area G 3rd floor corridor G351 and wall and ceiling rough in stairwell G. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover
|
Electrical Rough-In | 4/24/2015 | 4/24/2015 | 4/24/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in ceiling soffit inspection IL area F 2nd floor rooms F201-F207 ; F209. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/23/2015 | 4/23/2015 | 4/23/2015 | A | PASS |
Bob Reichert
|
|
|
Rough in inspection IL area G 1st and 2nd floor corridor walls G151 ; G251. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/17/2015 | 4/17/2015 | 4/17/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection IL area F 3rd floor ceiling soffit rooms: F301-F307, and F309. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/13/2015 | 4/13/2015 | 4/13/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection IL building area F 4th floor soffits all rooms, IL area F 1st floor rooms F151, F152, F155, F156, F157 and 2nd floor rooms F251, F252, F255, F256, F257. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 4/6/2015 | 4/6/2015 | 4/6/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in wall inspection IL area ''F'' 3rd and 4th floor corridor and rooms: F351, F352, F355, F356, F451, F452, F453, F455, and F456. Stairwell walls and ceilings F1 and F2. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 3/24/2015 | 3/26/2015 | 3/26/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection walls and ceiling IL area F and G 3rd floor rooms F356, G301-G305, and corridor ceiling pre rock G351. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 3/17/2015 | 3/18/2015 | 3/18/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in walls and ceilings IL area G 2nd floor rooms G202, G204-G207. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 3/11/2015 | 3/12/2015 | 3/12/2015 | P | PASS |
Bob Reichert
|
|
|
Rough in inspection for corridor ceiling pre rock IL area G 1st floor Corridor G151. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
|
Electrical Rough-In | 3/6/2015 | 3/9/2015 | 3/9/2015 | A | PASS |
Bob Reichert
|
|
|
Rough-in inspection IL area G 2nd floor rooms G201 and G203 and Corridor ceiling pre rock G251. Building permit number BLD13-00187. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover areas as requested
|
Electrical Rough-In | 2/11/2015 | 2/12/2015 | 2/12/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection IL area ''F'' 4th floor rooms: F401-F407 ; F409. Building permit # BLD13-00187. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover as per
|
Electrical Rough-In | 2/11/2015 | 2/11/2015 | 2/11/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in IL area ''F'' 3rd floor rooms: F301-F307 ; F309. Building permit # BLD13-00187. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover
|
Electrical Rough-In | 2/10/2015 | 2/10/2015 | 2/10/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection IL area ''F'' 2nd floor rooms: F201-F207 ; F209. BLDG permit # BLD13-00187. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover rooms as identified
|
Electrical Rough-In | 2/10/2015 | 2/10/2015 | 2/10/2015 | P | CANC |
Bob Reichert
|
|
|
Rough-in inspection SNF ''J" patient rooms: J01-J16, rooms only. Call Lonny when on-site. Thanks. Phone #: ###-#### >> Inspection requested via web by Lonny Baum Inspection cancelled from web by: Lonny Baum
|
Electrical Rough-In | 2/6/2015 | 2/6/2015 | 2/6/2015 | P | PASS |
Daryl DeGrange
|
|
|
Re-inspection on IL area ''F'' on rooms that had broken receptacle boxes. Call Lonny when on-site. Thanks, Lonny Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in area to be inspected completed rough-in ok cover
|
Electrical Rough-In | 2/3/2015 | 2/4/2015 | 2/4/2015 | A | PART |
Daryl DeGrange
|
|
|
Rough-in inspection IL area ''F'' 1st floor rooms: F101, F102, F103, F104, F105, F106, F107, ; F109 and area ''F'' 4th floor Corridor ceiling F451. Building permit # BLD13-00187. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum Partial r/i ok cover 4th floor corredor ceiling only
|
Electrical Rough-In | 1/23/2015 | 1/23/2015 | 1/23/2015 | P | PASS |
Daryl DeGrange
|
|
|
Rough-in inspection for IL area ''F'' corridor ceilings ; F351 pre-rock. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum Rough-in ok cover as per
|
Electrical Rough-In | 1/13/2015 | 1/13/2015 | 1/13/2015 | P | PASS |
Daryl DeGrange
|
|
|
Wall rough-in inspection for sheer walls in IL area ''F'' 1st floor between rooms F105 ; F1046. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-ok cover sheer wall only
|
Electrical Rough-In | 12/19/2014 | 12/19/2014 | 12/19/2014 | P | PASS |
Bob Reichert
|
|
|
Electrical rough-in for IL area "F" 1st ; 2nd floor corridor ceilings F151 ; F251. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ri ok as requested
|