Final | 11/28/2014 | 11/28/2014 | 11/28/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Blackham final ok
|
Final | 11/25/2014 | 11/26/2014 | 11/28/2014 | P | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Blackham 210.8 storage areas and unihabitale rooms require GFI protection 314.20 box shall not be set back of finished surface 250.80 grounding of metal boxes required
|
Permanent Service | 8/27/2014 | 8/28/2014 | 8/28/2014 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brandon Blackham. P/S Connect ok. Needs to thread in mast few more threads.Contractor stated he would take care of it before he called in for service. Concrete encased electrode needs to be put in wall or baried in concrete.
|