Final | 12/11/2014 | 12/12/2014 | 12/12/2014 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey ok final
|
Permanent Service | 9/17/2014 | 9/17/2014 | 9/17/2014 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey p/s u/g n ok
|
Electrical Rough-In | 9/8/2014 | 9/9/2014 | 9/9/2014 | A | PASS |
Bob Reichert
|
|
|
not the service Phone #: ###-#### Inspection requested via web by Neal Rumsey ri ok
|
Electrical Rough-In | 9/1/2014 | 9/3/2014 | 9/3/2014 | A | FAIL |
Bob Reichert
|
|
|
if you have questions please call eric at ###-#### We have not done the service yet waiting for some material Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 334.23 shall protect nm cable within 6' of attic access, 334.30 shall secure nm cable every 4 1/2' and within 12" of box, 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member or use steel plate, 210.52(A)(1) receptacles shall be installed such that no point along floor line is more than 6' from outlet, BCC shall provide boxes for free conductors #12 and #14l
|