Final | 4/28/2015 | 4/29/2015 | 4/29/2015 | A | PASS |
Bob Reichert
|
|
|
Request final. Owner will unlock residence in am. Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence ok final
|
Final | 2/27/2015 | 3/2/2015 | 3/2/2015 | A | FAIL |
Bob Reichert
|
|
|
Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence called, left message, left correction notice, BCC 50% energy efficient bulbs shall be installed, 4-05-23 shall inspect depth of raceway to garage, 110.26 shall provide 3' clearance in front of panel, 250.32B shall not connect grounding electrode to grounded conductor, 250.66 shall provide 2 grounding electrodes at garage
|
Final | 2/26/2015 | 2/27/2015 | 2/27/2015 | A | FAIL |
Cevyn Recla
|
|
|
Tim. ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence Called Tim Boise Energy code, 50% minimum lamps must be energy efficient BCC 4.05.23 No undergtround inspection record 110.26 1 working space about electrical equipment required, 3 feet at meter main 250.32.b1 Seperate buildings grounded conductor shall be connected to equipment grounding conductor
|
Rough-In Permanent Service | 9/15/2014 | 9/16/2014 | 9/16/2014 | A | PASS |
Bob Reichert
|
|
|
Electrical Rough in. Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence ri ok, NOTE: no u/g house to garage seen yet, will change room count to 10 rooms, p/s u/g n ok
|