Permit Information
Permit NumberELE14-02507
StatusFinaled
Name BENDER ELECTRIC SERVICES
Site Address 417 W ADA ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Complete remodel rewire
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/22/201410/23/201410/23/2014APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by kendall bender final ok
Final10/22/201410/22/201410/22/2014PFAIL
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by kendall bender 334.15(B)- exposed nm cable feeding furnace needs protection . also need disconnect at furnace or lockoff on breaker. No access to furnace yesterday because of floor contractors.
Final10/21/201410/22/201410/22/2014ACANC
DetailsRex Boyles
Phone #: ###-#### >> Inspection requested via web by kendall bender Inspection cancelled from web by: kendall bender
Final10/21/201410/21/201410/21/2014PFAIL
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by kendall bender 210.8(A)(6)-All 120volt receptacles serving countertop in kitchen shall have GFCI protection, 210.8(A)7- laundry where receptacles are within 6 ' of sink shall have GFCI protection. 300.5-120 volt feed to existing garage unknown depth requires GFCI protection
Permanent Service9/10/20149/11/20149/11/2014APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by kendall bender correction made p/s o/h rec ok
Electrical Rough-In9/10/20149/11/20149/11/2014APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by kendall bender corrections made r/i ok
Permanent Service9/9/20149/10/20149/10/2014AFAIL
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by kendall bender 310.15(B)(7)--service entrance conductors need to be rated 83%of service rating
Electrical Rough-In9/9/20149/10/20149/10/2014AFAIL
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by kendall bender 334.30 secure nm cable within 12in. of enclosure. 300.4 1/14in from edge of stud to bored holes or nm cable.