Final | 10/22/2014 | 10/23/2014 | 10/23/2014 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender final ok
|
Final | 10/22/2014 | 10/22/2014 | 10/22/2014 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 334.15(B)- exposed nm cable feeding furnace needs protection . also need disconnect at furnace or lockoff on breaker. No access to furnace yesterday because of floor contractors.
|
Final | 10/21/2014 | 10/22/2014 | 10/22/2014 | A | CANC |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender Inspection cancelled from web by: kendall bender
|
Final | 10/21/2014 | 10/21/2014 | 10/21/2014 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 210.8(A)(6)-All 120volt receptacles serving countertop in kitchen shall have GFCI protection, 210.8(A)7- laundry where receptacles are within 6 ' of sink shall have GFCI protection. 300.5-120 volt feed to existing garage unknown depth requires GFCI protection
|
Permanent Service | 9/10/2014 | 9/11/2014 | 9/11/2014 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender correction made p/s o/h rec ok
|
Electrical Rough-In | 9/10/2014 | 9/11/2014 | 9/11/2014 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender corrections made r/i ok
|
Permanent Service | 9/9/2014 | 9/10/2014 | 9/10/2014 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 310.15(B)(7)--service entrance conductors need to be rated 83%of service rating
|
Electrical Rough-In | 9/9/2014 | 9/10/2014 | 9/10/2014 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 334.30 secure nm cable within 12in. of enclosure. 300.4 1/14in from edge of stud to bored holes or nm cable.
|