Final | 10/1/2014 | 10/2/2014 | 10/2/2014 | A | PASS |
Bob Reichert
|
|
|
Need ceiling inspection also. Call if can not get in I will give you the lockbox code Phone #: ###-#### Inspection requested via web by robert feller corrections made, ok cover ceiling, ok final, signed card
|
Final | 9/30/2014 | 10/1/2014 | 10/1/2014 | A | FAIL |
Bob Reichert
|
|
|
Need ceiling inspection also. Call if you can''t get in I will give you the lockbox code Phone #: ###-#### Inspection requested via web by robert feller called, left correction notice, NEC 358.30(A) shall securely fasten emt within 3' of panel, 330.30(B) shall securely strap mc within 12" of termination, 210.8(B)(5) shall provide gfci outlet within 6' of sink, 408.4 circuit directory shall be clear, concise, and specific for it's purpose, 725.25 all class 2, 3 , pltc cables shall be removed if abandoned, 300.11(A) cables and raceways shall not be supported by ceiling grid, BCC no violations shall be retained
|
Electrical Rough-In | 9/11/2014 | 9/11/2014 | 9/11/2014 | P | PASS |
Rock A. Hudson
|
|
|
Bob Phone #: ###-#### Wall rough in ok cover
|