Permit Information
Permit NumberELE14-02598
StatusFinaled
Name R M E INC
Site Address 6399 N GLENCREST WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Upgrade existing service to 200 amp. Wire outlets and lights in shed.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/7/20151/8/20151/8/2015PPASS
DetailsCevyn Recla
Paul. After 1:30. Code #11405. Phone #: ###-#### Inspection requested via web by Sean DeLacy
corrections made, final OK
Final1/5/20151/6/20151/6/2015PFAIL
DetailsCevyn Recla
Paul. After 1:30. Code #11405. Phone #: ###-#### Inspection requested via web by Sean DeLacy
210.8.A.2 GFCI protection required in accessory building with floor at or below grade level, not intended as habitable room, and limited to storage area, work area, or similar use
Spoke to Paul
Final12/12/201412/12/201412/12/2014PFAIL
DetailsDaryl DeGrange
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy NEC 310.4(B) Multiwire branch circuits shall simultanously diconnect all ungrounded conductors. NEC 406.8(B) Receptacles installed in wet locations shall be listed weather-resistant type(shed) NEC 406.11 Required tamper-resistant receptacles.(shed) NEC 408.36 Back-fed devices shall be secured inplace (shed)
Electrical Rough-In9/18/20149/19/20149/19/2014APASS
DetailsRex Boyles
Paul. Shed. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i rear bldg. ok NOTE: look for thwn conductors in u.g. feed at final
Permanent Service9/17/20149/18/20149/18/2014PPASS
DetailsRex Boyles
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy p/s u/g rec ok
Electrical Rough-In9/18/20149/18/20149/18/2014PPASS
DetailsRex Boyles
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i ok underground conduit to rear bldg.
Permanent Service9/17/20149/17/20149/17/2014PNR
DetailsRex Boyles
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy was called in for 9/18/14 according to RME. called and asked camille to call back in