Final | 1/7/2015 | 1/8/2015 | 1/8/2015 | P | PASS |
Cevyn Recla
|
|
|
Paul. After 1:30. Code #11405. Phone #: ###-#### Inspection requested via web by Sean DeLacy corrections made, final OK
|
Final | 1/5/2015 | 1/6/2015 | 1/6/2015 | P | FAIL |
Cevyn Recla
|
|
|
Paul. After 1:30. Code #11405. Phone #: ###-#### Inspection requested via web by Sean DeLacy 210.8.A.2 GFCI protection required in accessory building with floor at or below grade level, not intended as habitable room, and limited to storage area, work area, or similar use Spoke to Paul
|
Final | 12/12/2014 | 12/12/2014 | 12/12/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy NEC 310.4(B) Multiwire branch circuits shall simultanously diconnect all ungrounded conductors. NEC 406.8(B) Receptacles installed in wet locations shall be listed weather-resistant type(shed) NEC 406.11 Required tamper-resistant receptacles.(shed) NEC 408.36 Back-fed devices shall be secured inplace (shed)
|
Electrical Rough-In | 9/18/2014 | 9/19/2014 | 9/19/2014 | A | PASS |
Rex Boyles
|
|
|
Paul. Shed. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i rear bldg. ok NOTE: look for thwn conductors in u.g. feed at final
|
Permanent Service | 9/17/2014 | 9/18/2014 | 9/18/2014 | P | PASS |
Rex Boyles
|
|
|
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy p/s u/g rec ok
|
Electrical Rough-In | 9/18/2014 | 9/18/2014 | 9/18/2014 | P | PASS |
Rex Boyles
|
|
|
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i ok underground conduit to rear bldg.
|
Permanent Service | 9/17/2014 | 9/17/2014 | 9/17/2014 | P | NR |
Rex Boyles
|
|
|
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy was called in for 9/18/14 according to RME. called and asked camille to call back in
|