Permit Information
Permit NumberELE14-02675
StatusFinaled
Name R M E INC
Site Address 2755 S BEVERLY ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Install service, lights & outlets per plan for new office/warehouse & site.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/13/20153/16/20153/16/2015APASS
DetailsRock A. Hudson
Meter Pedestal. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Final ok
Permanent Service3/13/20153/16/20153/16/2015APASS
DetailsRock A. Hudson
This is for the meter pedestal for the (2) City of Boise pole lights Phone #: ###-#### Inspection requested via web by Buster Bowen p/s u/g n ok
Final2/10/20152/10/20152/10/2015PPASS
DetailsRock A. Hudson
Chad is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Core and shell building 1 Final ok
Final2/6/20152/9/20152/9/2015AFAIL
DetailsRock A. Hudson
Toby is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 210.70- Emergency egress fixtures not receiving a charge.
408.4- Circuit directory shall be complete
Permanent Service1/20/20151/20/20151/20/2015PPASS
DetailsRock A. Hudson
Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Metal water pipe bond to be done when pipe present. p/s u/g n ok
Permanent Service1/19/20151/20/20151/20/2015AFAIL
DetailsRock A. Hudson
Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 250.24(A)(1)- The grounding electrode conductor connection shall be made at the same terminal or bus to which the grounded conductor is connected.
250.50- All available grounding electrodes shal be used to form grounding electrode system.
Electrical Rough-In10/22/201410/23/201410/23/2014APASS
DetailsRock A. Hudson
Site underground cover. Toby is the on site contact. Phone #: ###-#### Inspection requested via web by Buster Bowen

UG as noted on contractor print. RI OK to cover
Electrical Rough-In10/8/201410/9/201410/9/2014APASS
DetailsRock A. Hudson
Underground cover. Toby is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen Low volt conduits on south side of office bldg rough in ok cover
Electrical Rough-In9/25/20149/25/20149/26/2014PPASS
DetailsRock A. Hudson
Ufer inspection. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Concrete encased electrode on front office bldg rough in ok cover