DOC - Permit Expired | 2/1/2019 | 2/1/2019 | 2/1/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Electrical Rough-In | 10/30/2015 | 10/30/2015 | 10/30/2015 | P | PASS |
Rex Boyles
|
|
|
Logan Phone #: ###-#### corrections made r/i ok
|
Electrical Rough-In | 3/27/2015 | 3/30/2015 | 3/30/2015 | P | FAIL |
Rex Boyles
|
|
|
Jerry-please call 10 min prior to meet Phone #: ###-#### same corrections as last inspection plus j boxes in bsmt. need to be accessable
|
Electrical Rough-In | 3/17/2015 | 3/20/2015 | 3/20/2015 | P | FAIL |
Rex Boyles
|
|
|
Jerome Phone #: ###-#### 334.30-nm cable shall be supported and secured by stapling within 12" of box and every 41/2 feet. 300.4- (A)(1)-where a cable is ran thru bored holes, not less than 11/4" from hole to edge of stud. Nailpales required to fix problem. Make up ground wires prior to inspection. Use colorado jims or stackers for firred out walls to support nm cable.
|
Conference | 10/2/2014 | 10/3/2014 | 10/3/2014 | P | DONE |
Rock A. Hudson
|
|
|
Please call ahead for access/10mins - Jerry Phone #: ###-#### Discussed box fill, min required receptical outlets, GFCI protection of kitchen and bath, min. number of circuits serving kit counter and bathrooms. 6' rule for habitable rooms
|