Final | 10/13/2014 | 10/13/2014 | 10/13/2014 | P | PASS |
Rock A. Hudson
|
|
|
Lock box #8133 Please call Eric with any questions Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok
|
Permanent Service | 10/13/2014 | 10/13/2014 | 10/13/2014 | P | PASS |
Rock A. Hudson
|
|
|
Lock box #8133 Please call Eric with any questions Phone #: ###-#### Inspection requested via web by Eric Schroeder p/s o/h rec ok
|
Permanent Service | 10/3/2014 | 10/6/2014 | 10/6/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Re energize, power off over a year. Phone #: ###-#### Inspection requested via web by Eric Schroeder BCC- To energize service which has been off for extended period of time grounding shall be brought up to current code cycle, 2008. 250.53(A)(2)- Single piping system shall be supplemented by additional grounding electrode. 4-05-32- Code violation not to be retained. 334.40- NM cable splice or tap shall be in a box. NM cable shall not be installed where subject to physical damage.
|
Permanent Service | 10/3/2014 | 10/3/2014 | 10/3/2014 | P | CANC |
Rock A. Hudson
|
|
|
RE ENERGIZE, POWER OFF OVER A YEAR. Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|