Final | 2/12/2015 | 2/12/2015 | 2/12/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins Available fault current under 22k. will be posted when sign complete. Final ok
|
Final | 2/6/2015 | 2/6/2015 | 2/6/2015 | P | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins 210.8- Mech rm GFCI protect receptacle located with in 6' of sink. 110.24- Available fault current shall be posted on service. 406.5- Receptacle outlets shall be secured in place. Outdoor by east door.
No card posted. Temporary final ok
|
Final | 2/4/2015 | 2/4/2015 | 2/4/2015 | P | NR |
Rock A. Hudson
|
|
|
Looking to get temporary final this late afternoon and rest of final on friday. If we could time the inspection towards the end of the day today would be appreciate it. Phone #: ###-#### Inspection requested via web by Thomas Jenkins 314.25 All boxes shall have covers. Multiple covers missing that are accessible to public. Street light cover missing on parking lot light N.E. corner of store. All floor boxes. 6 gang in hall. Will rescedule
|
Permanent Service | 1/26/2015 | 1/26/2015 | 1/26/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins p/s u/g n ok
|
Electrical Rough-In | 1/23/2015 | 1/23/2015 | 1/23/2015 | P | PASS |
Rock A. Hudson
|
|
|
Ceiling inspection Phone #: ###-#### Inspection requested via web by Thomas Jenkins Grid rough in ok cover
|
Electrical Rough-In | 12/17/2014 | 12/17/2014 | 12/17/2014 | P | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins Office and bathroom walls and hard lid rough in ok cover
|
Electrical Rough-In | 10/24/2014 | 10/27/2014 | 10/27/2014 | A | PASS |
Bob Reichert
|
|
|
Underground inspection for pad. Phone #: ###-#### Inspection requested via web by Thomas Jenkins
Floor outlets, slab cover ok
|
Electrical Rough-In | 10/8/2014 | 10/8/2014 | 10/8/2014 | A | PASS |
Rock A. Hudson
|
|
|
Underground and ufere Phone #: ###-#### Inspection requested via web by Thomas Jenkins underground for light pole bases and concrete encased rough in ok cover
|