Final | 12/8/2014 | 12/9/2014 | 12/9/2014 | A | PASS |
Rock A. Hudson
|
|
|
Inspection requested via web by HZ ZAHIC Final ok
|
Rough-In Permanent Service | 10/13/2014 | 10/13/2014 | 10/13/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by HZ ZAHIC corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 10/12/2014 | 10/13/2014 | 10/13/2014 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested via web by HZ ZAHIC no phone number, left correction notice, NEC 334.23 shall protect nm cable within 6' of attic access, 250.64(C) grounding electrode conductor (gec) shall be continuous, i.e. each panel shall have separate gec from grounding electrode, builder will call electrical contractor
|