Permit Information
Permit NumberELE14-02819
StatusFinaled
Name BENDER ELECTRIC SERVICES
Site Address 12336 W OVERLAND RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: new commercial building lighting and power
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/11/20155/11/20155/11/2015PPASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by kendall bender corrections made final ok
Final5/8/20155/8/20155/8/2015AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender 358.26- Max number of bends between pull points with EMT shall not exceed 360 degrees. run to fire panel
410.46- Luminaires with exposed metal parts shall have means of connecting equipment grounding conductor. No lug ran thru hole in base
Permanent Service4/23/20154/23/20154/23/2015PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender Correction made p/s u/g n ok House panel
Permanent Service4/21/20154/22/20154/22/2015AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender Corrections not complete. 240.24(A)- Top breaker height shall not exceed 6'7".
250.119- Grounding electode and equipment ground conductors shall be identified bare or green.
Tryed to call 2 times no answer or voice mail on either call
Permanent Service4/17/20154/17/20154/17/2015PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender
110.24- AIC rating shall be calculated and posted with available fault current and date calculated prior to permanent service.
240.24(A)- Overcurrent devices shall be installed so the operating handle in it's highest point does not exceed 6'7".
Electrical Rough-In4/13/20154/14/20154/14/2015PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender Perimeter and demizing walls only rough in ok cover
Conference4/13/20154/13/20154/13/2015PDONE
DetailsRock A. Hudson
Making note of more than 1 permit exists on this building ele15-01002 for TI
Electrical Rough-In3/24/20153/25/20153/25/2015APASS
DetailsRock A. Hudson
under slab floor boxes Phone #: ###-#### Inspection requested via web by kendall bender 3 floor boxes and conduits south end of building rough in ok cover
Temporary Service12/11/201412/11/201412/11/2014PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender t/s u/g n ok
Temporary Service12/9/201412/10/201412/10/2014AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender 110.12(A)- Unused openings shall be closed.
250.4(A)(1)- Electrical equiptment shall be connected to earth with a method described in 250.53.
310.16- #10 THHN conductors not rated for 50 amp overcurrent protection.
Install panel cover
Final11/7/201411/10/201411/10/2014ACANC
DetailsRock A. Hudson
pole bases Phone #: ###-#### Inspection requested via web by kendall bender Needed rough in inspection
Electrical Rough-In11/10/201411/10/201411/10/2014PPASS
DetailsRock A. Hudson
pole bases Phone #: ###-#### Inspection requested via web by kendall bender Pole base rough in ok pour
Electrical Rough-In11/6/201411/7/201411/7/2014APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender Underground for pole bases rough in ok cover
Electrical Rough-In10/9/201410/10/201410/10/2014APASS
DetailsDaryl DeGrange
Uffer inspection Phone #: ###-#### Inspection requested via web by kendall bender Rough-in ok cover concrete enecased electrode