Final | 12/12/2014 | 12/12/2014 | 12/12/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey
|
Final | 12/11/2014 | 12/12/2014 | 12/12/2014 | A | FAIL |
Rock A. Hudson
|
|
|
call for code Phone #: ###-#### Inspection requested via web by Neal Rumsey 210.8 All receptical outlets located within 6' of sink shall have GFCI protection. up bed by vanity. 210.8- All receptical outlets located in garage shall have GFCI protection. Rev polarity garage GFI.
|
Rough-In Permanent Service | 10/15/2014 | 10/16/2014 | 10/15/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 10/13/2014 | 10/14/2014 | 10/14/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey 300.4- NM cable shall be installed where not subject to physical damage. Upstairs by return air. 314.3- NM cable shall terminate in a box, laundry rm and out lights
|