Permit NumberELE14-02852
StatusFinaled
Name RUSSELL CHARLES S
Site Address 2320 N 26TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/21/201911/21/201911/21/2019APASS
DetailsMark Moncarr
This was an aging inspection for corrections needing to be made. Previous homeowner no longer lives there. Was able to talk to new homeowner and he allowed me to look to see if corrections were made. There was a panel in the bathroom that was relocated to opposite side of wall. Corrections were made as per Rock Hudsons notes. Ok final.
ELE-Aging Inspection11/18/201911/18/201911/19/2019 DONE
DetailsMark Moncarr
Knocked on door at 930am on 11/19/19 no answer. Left notice in mailbox beside front door. Asked to contact me if corrections were made, and to call for a final inspection. If not, to please call with progress on work done.
ELE-Aging Inspection8/19/20198/19/20198/19/2019 FAIL
DetailsMark Moncarr
Final inspection needed.
ELE-Aging Inspection5/9/20195/9/20195/17/2019 DONE
DetailsMark Moncarr
Please coordinate time to conduct a final inspection.
ELE-Aging Inspection2/7/20192/7/20192/12/2019 DONE
DetailsMark Moncarr
Called number listed on 2/12/19 at 10:02 AM. Number no longer in service.
Final4/14/20154/15/20154/15/2015AFAIL
DetailsRock A. Hudson
Charles// please call before Phone #: ###-#### 210.8- All receptacle outlet 15 or 20 amp 120 volt shall have GFCI protection.
406.12- All 15 or 20 amp 120 volt receptacle outlets shall be tamper resistant type. Only few were rewired.
240.24(E)- Over current devices shall not be located in a bathroom.
4-05-31- Panel location shall not be installed in a bathroom.
Final4/13/20154/14/20154/14/2015ANH
DetailsDaryl DeGrange
Charles Phone #: ###-#### No access wrong contact phone number.
Electrical Rough-In1/23/20151/26/20151/26/2015PPASS
DetailsCevyn Recla
Charlie Phone #: ###-####
need ungrounded conductors to be permanently reidentified, and grounds moved to gournd bar seperated from neutral in subpanel.
RI ok to cover
Conference10/14/201410/15/201410/15/2014ADONE
DetailsBob Reichert
Charles Phone #: ###-#### talked about re-wiring house, bringing up to code, free conductor, 1 1/4", when to call for ri