Final | 12/29/2014 | 12/29/2014 | 12/29/2014 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov corrections made, final ok
|
Final | 12/24/2014 | 12/24/2014 | 12/24/2014 | P | FAIL |
Cevyn Recla
|
|
|
Garage code 3283 Thank you and merry christmas Phone #: ###-#### Inspection requested via web by daniel bibikov called contractor 422.11 overcurrent protection shall not exceed nameplate rating of appliance 334.12 NM shall not be used in damp or wet locations 422.31 Disconnecting means shall be provided for permanently installed appliances
|
Rough-In Permanent Service | 10/24/2014 | 10/24/2014 | 10/24/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov crrections made r/i ok p/s u/g n ok
|
Rough-In Permanent Service | 10/23/2014 | 10/24/2014 | 10/24/2014 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov still need to confirm sch 80 for id.power 2" under slip joint. 330.4 -11/4" above panel and exterior walls.
|
Rough-In Permanent Service | 10/23/2014 | 10/23/2014 | 10/23/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov
300.4 Bored holes, wiring shall be protected from damage 352.10F note: Type sch 80 identified for areas of physical damage
250.148 boxes with multiple circuits, all grounding shall be tied together
|